AC-side
Max. cable cross-section (without wire sleeves)
50mm²
Min. cable cross-section
0
Length of insulation to be stripped off
dependent on the utilised terminal type
Tightening torque
2.5 - 4 Nm / 4 - 4.5 Nm (39.0-48.0TL3) Nm
Connection type
Screw terminal
Ground conductor connection
M8
Fuse protection for installation provided by customer
100 A at 35mm² / 63 A at 16 mm²
Fitting for AC connection
M50
Cable diameter for cable fitting
11 - 17 (M25) 5 - 9.5 (M16) mm
Torque for cable fitting
4 (M25) 1.5 (M16) Nm
Interfaces
Interface screw connections
Ethernet: M25, default RS485: M16, max. 1.5 mm
Cable diameter for cable fitting
11 - 17 (M25) 5 - 9.5 (M16) mm
RS485 connection type
Connector
RS485 terminal cable cross-section
0.25 - 1.5 mm²
Ethernet connection type
RJ45
Torque for cable fitting
4 (M25) 1.5 (M16) Nm
7.5
Connecting the device to the power grid
7.5.1
Prepare the grid connection
TN-S system
↻
Connection cable with 5 strands is provided on the device.
↻
Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_46].
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25 mm].
»
Make the grid connection.
1
2
Fig. 27:
Terminals
1
AC side
2
DC-side
Powador 30.0-72.0 TL3