Table 40: JNP10K-PWR-AC2 Power Cable Specifications for 20-A Input (continued)
Graphic
Spare Juniper
Model Number
Plug Standards
Cord Set Rating
Locale
JNP10K-PWR-AC2 Power Cable Specifications for 30-A Input
The JNP10K-PWR-AC2 HVAC or HVDC power supplies requires a high current cable assembly when set
for 30-A input. One end of the cable has an Anderson APP-400 connector, the other end of the cable is
bare wire. See
and
. These cables are separately orderable and
are not shipped automatically with JNP10K-PWR-AC2 orders. An example of the right-angle cable and
connector is shown in
.
For connection to AC systems, Juniper provides a cable with either a NEMA 30-A connector
(
) or an IEC 330P6W connector (
).
Figure 45: NEMA 30-A Connector
g100610
Figure 46: IEC 330P6W Connector
g100616
113
Содержание MX10008
Страница 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Страница 19: ......
Страница 89: ......
Страница 129: ......
Страница 170: ......
Страница 179: ...Figure 76 Removing Fan Tray JNP10008 FAN from an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 181 ...
Страница 183: ...Figure 79 Installing Fan Tray JNP10008 FAN in an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 185 ...
Страница 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Страница 279: ......
Страница 287: ......
Страница 318: ...Restricted Access Warning 321 ...
Страница 333: ...Jewelry Removal Warning 336 ...
Страница 336: ...Operating Temperature Warning 339 ...
Страница 345: ...DC Power Disconnection Warning 348 ...
Страница 349: ...DC Power Wiring Sequence Warning 352 ...
Страница 352: ...DC Power Wiring Terminations Warning 355 ...
Страница 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...