Table 30: Rack Requirements for the MX10008
Guidelines
Rack Requirement
Use a four-post rack that provides bracket holes or hole patterns spaced
at 1 U (1.75 in. or 4.45 cm) increments and that meets the size and
strength requirements to support the weight.
A U is the standard rack unit defined in Cabinets, Racks, Panels, and
Associated Equipment (document number EIA-310–D) published by the
Electronics Industry Association.
You can stack three MX10008 routers if:
•
The rack is 39 U or greater.
•
The rack meets the strength requirements to support the weight.
•
The facility can provide adequate power and cooling.
Rack type: four-post
The holes in the rack mount kit are spaced at 1 U (1.75 in. or 4.45 cm),
so that the router can be mounted in any rack that provides holes spaced
at that distance.
Rack mount kit hole spacing
•
Ensure that the rack complies with the standards for a 19-in. wide
rack as defined in Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry
Association.
•
Use one of the standard rack lengths as defined in the four-part
Equipment Engineering (EE); European telecommunications standard for
equipment practice (document numbers ETS 300 119-1 through 119-4)
published by the European Telecommunications Standards Institute
•
23.62 in. (600 mm)
•
30.0 in. (762 mm)
•
31.5 in. (800 mm)
•
Ensure that the rack rails are spaced widely enough to accommodate
the router chassis’ external dimensions. The outer edges of the flange
extend the chassis width to 19 in. (48.26 cm).
•
Ensure that the rack is strong enough to support the weight of the
router and cabling.
•
Ensure that the spacing of rails and adjacent racks allows for proper
clearance around the router and rack. See
Requirements for Airflow and Hardware Maintenance” on page 98
Rack size and strength
97
Содержание MX10008
Страница 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Страница 19: ......
Страница 89: ......
Страница 129: ......
Страница 170: ......
Страница 179: ...Figure 76 Removing Fan Tray JNP10008 FAN from an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 181 ...
Страница 183: ...Figure 79 Installing Fan Tray JNP10008 FAN in an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 185 ...
Страница 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Страница 279: ......
Страница 287: ......
Страница 318: ...Restricted Access Warning 321 ...
Страница 333: ...Jewelry Removal Warning 336 ...
Страница 336: ...Operating Temperature Warning 339 ...
Страница 345: ...DC Power Disconnection Warning 348 ...
Страница 349: ...DC Power Wiring Sequence Warning 352 ...
Страница 352: ...DC Power Wiring Terminations Warning 355 ...
Страница 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...