Follow these environmental guidelines:
•
The site must be as dust-free as possible, because dust can clog air intake vents and filters, reducing the
efficiency of the router cooling system.
•
Maintain ambient airflow for normal router operation. If the airflow is blocked or restricted, or if the
intake air is too warm, the router might overheat, leading to the router temperature monitor shutting
down the device to protect the hardware components.
provides the required environmental conditions for normal router operation.
Table 28: MX10000 Environmental Tolerances
Tolerance
Description
No performance degradation up to 6000 feet (1829 meters).
Altitude
Normal operation ensured in relative humidity range of 5% through 90%,
noncondensing.
•
Short-term operation ensured in relative humidity range of 5% through
93%, noncondensing.
NOTE:
As defined in NEBS GR-63-CORE, Issue 3, short-term events can
be up to 96 hours in duration but not more than 15 days per year.
Relative humidity
•
Normal operation ensured in temperature range of 32° F through 104° F
(0° C through 40° C).
NOTE:
The chassis can be temporarily be operated at 45° C at sea level
for up to 1% of the time ( 3.65 days per year).
•
Nonoperating storage temperature in shipping container: –40° F through
158° F (–40° C through 70° C).
•
Short-term operation ensured in temperature range of 32°F through
104°F (0°C through 40°C) at 6000 ft altitude and 32°F through 114.8°F
(0°C through 46°C) at sea-level.
NOTE:
As defined in NEBS GR-63-CORE, Issue 3, short-term events can
be up to 96 hours in duration but not more than 15 days per year.
Temperature
Designed to comply with Zone 4 earthquake requirements per NEBS
GR-63-CORE, Issue 3.
Seismic
93
Содержание MX10008
Страница 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Страница 19: ......
Страница 89: ......
Страница 129: ......
Страница 170: ......
Страница 179: ...Figure 76 Removing Fan Tray JNP10008 FAN from an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 181 ...
Страница 183: ...Figure 79 Installing Fan Tray JNP10008 FAN in an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 185 ...
Страница 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Страница 279: ......
Страница 287: ......
Страница 318: ...Restricted Access Warning 321 ...
Страница 333: ...Jewelry Removal Warning 336 ...
Страница 336: ...Operating Temperature Warning 339 ...
Страница 345: ...DC Power Disconnection Warning 348 ...
Страница 349: ...DC Power Wiring Sequence Warning 352 ...
Страница 352: ...DC Power Wiring Terminations Warning 355 ...
Страница 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...