Art. No. DS 4092 TS
ON
OFF
TOGGLE
pressed.
This is only visible if "Function channel 1
(2) = Switching (1 bit)"!
Value of the button for
Channel 1 (2)
(0...255)
0
...255
This parameter defines the object value
transmitted to the bus when the button is
pressed.
It is only visible if "Function channel 1
(2) = Value transmitter 0...255 (1 byte)"!
Value of the button for
Channel 1 (2)
(0...100 %)
0
...100
This parameter defines the object value
transmitted to the bus when the button is
pressed.
It is only visible if "Function channel 1
(2) = Value transmitter 0...100% (1
byte)"!
Temperature value of
the button for channel 1
(2)
(0 … 40 °C)
0...
20
...40
This parameter defines the temperature
value transmitted to the bus when the
button is pressed.
It is only visible if "Function channel 1
(2) = Temperature value transmitter (2
bytes)"!
Time between channel
1 and channel 2
(1...255 x 100 ms)
0...
30
...255
Depending on the selected operation
concept, this parameter defines the
interval at which the push button
transmits the telegram for channel 1 and
the telegram for channel 2 when the
button is pressed.
h
PB LED (Only visible when the LED display function is enabled on the application program
of Version 1.2!)
Function
The rotary sensor has a red Status LED,
which is assigned to the push-button.
The Status LED can execute various
display functions, provided that its use is
generally enabled on the parameter
page "Push-button (PB) / Rotary knob
(RK)".
The LED display function can only be
configured and used with Version 1.2 of
the application program! This parameter
is not available when Version 1.1 of the
application program is being used. The
Status LEDs are then only activated
when an active alarm is signalling.
always OFF
In this configuration, the Status LED
remains permanently switched off.
Special case: In this setting, the Status
LED displays adjustments of the
transmission values in the "Value
transmitter" push-button function,
Page 106 of 143
Software "Rotary sensor with extensions 10FE1x"
Parameters