Art. No. DS 4092 TS
Function of the push-
button
Reaction "as push-button on
pressing"
Reaction "as push-button on
releasing"
Switching / toggling
Switching telegram
Switching telegram
Dimming
Switching telegram
No telegram
Venetian blind
Move telegram
No telegram
Scene extension
Scene recall telegram
No telegram
1-byte value transmitter Value telegram
No telegram
2-byte value transmitter Value telegram
No telegram
2-channel operation
Channel 1: 1-bit object
type
Switching telegram
No telegram
2-channel operation
Channel 1: 1-byte
object type
Value telegram
No telegram
2-channel operation
Channel 1: 2-byte
object type
Temperature value telegram
No telegram
No function
No telegram
No telegram
Telegram reactions on disabling and re-enabling depending on the push-button functions
o
Set the parameter "Reaction of push-button at the beginning / end of disabling" to
"Reaction as disabling function push-button on pressing" or "Reaction as disabling function
push-button on releasing".
The push-button executes the function specified by the disabling function of the push-
button. The disabling function is an internal button function with independent
communication objects and independent parameters on the parameter page "PB - disabling
function". The setting possibilities available for this disabling function are the same as for
the push-button itself.
The configuration of the disabling function is executed. If the configuration has no function
or does not transmit a telegram on pressing or releasing the button, then there is no
reaction to disabling or re-enabling either.
The table above shows all possible telegram reactions of the device depending on the
configuration of the disabling function for this setting, too. The telegrams are transmitted to
the bus via the communication object of the disabling function.
Configuring the reaction of the push-button during a disable
Regardless of the behaviour at the beginning or end of disabling, the push-button can be
influenced separately during disabling.
The disabling function must have been enabled in advance.
o
Set the parameter "Behaviour of the push-button during disabling" to "no function".
The push-button is completely disabled during disabling. Pressing a button has no effect.
The buzzer then no longer signals any operations either while it is configured to "button-
press display".
o
Set the parameter "Behaviour of the push-button during disabling" to "as disabling function
push-button".
The push-button behaves as specified by the configuration of the disabling function. The
telegrams are transmitted to the bus via the communication objects of the disabling
function. The buzzer then no longer signals any operations either while it is configured to
"button-press display".
Page 75 of 143
Software "Rotary sensor with extensions 10FE1x"
Functional description