Art. No. DS 4092 TS
provided that this function has been
enabled in the ETS and is executed by
the operator. The LED then lights up
briefly when a new value adjustment
telegram is transmitted.
always ON
In this configuration, the Status LED
remains permanently switched on.
Permanently switched-on Status LEDs
can be used, for example, for orientation
lighting.
Special case: In this setting, the
continuous light is interrupted for the
length of the value adjustment (function:
value transmitter with adjustment
function for the push-button). The LED
lights up briefly for each adjustment
value transmitted to the bus.
Button-press display
If the Status LED is working as a button-
press display, it lights up when the push-
button is pressed and released
(exception: Scene extension with
memory function: Here, after short
operations, the LED only lights up on
release). In addition, the LED signals to
the push-button when a storage
telegram is being transmitted in the
function "Scene extension". In addition,
in the "Value transmitter" function, the
LED displays the transmission of a value
adjustment telegram.
The light period of the button-press
display can generally be set in the ETS
using the "Light period of the Status
LED for button-press display"
parameter. In contrast to this, the signal
duration of the display for a scene
storage telegram (approx. 3 seconds)
and the value adjustment (250
milliseconds) is permanently defined.
Telegram acknowledgment As an alternative to the button-press
display, the telegram acknowledgment
can then be configured. The telegram
acknowledgment only signals the
transmission of telegrams in the function
"2-channel operation" (fixed display
period 250 milliseconds). Other
operations of the rotary knob or push-
button are not displayed after the
telegram acknowledgement.
Status indication
Irrespective of the configuration of the
push-button, the status LED can indicate
the state of a separate LED
communication object. Here, the LED
can be switched on or off statically via
the 1-bit object value received. In this
setting, the object value is not displayed
in inverted form by the LED
(Object = "0" -> LED = OFF /
Object = "1" -> LED = ON).
Page 107 of 143
Software "Rotary sensor with extensions 10FE1x"
Parameters