Art. No. DS 4092 TS
configured telegram to the bus (contact
closed at the input = telegram as with
rising edge; contact open at input =
telegram as with falling edge).
The selection of the settings of this
parameter depends on the configured
edge evaluation of the input.
h
Ex - disable transmit cyclically (X = 1, 2, 3) - Only for the "Switching" function!
Cyclical transmission ?
Optionally, the object values can be
transmitted cyclically to the bus for the
"Switching" function. For this, the
transmission criteria must first be
defined in the ETS. This parameter
specifies with which value cyclical
transmission should take place.
The object value entered in the
switching objects by the device on a
edge change or externally by the bus is
always transmitted cyclically. The object
value is then also transmitted cyclically
when "no reaction" is assigned to a
rising or falling edge. Cyclical
transmission also takes place directly
after bus voltage return, if the reaction
after bus voltage return corresponds to
the transmission criterion for cyclical
transmission. During an active disable,
no cyclical transmissions take place via
the disabled input.
no cyclical transmission
There is no cyclical transmission.
Repeat on ON
Transmission takes place cyclically
when the object value is "ON".
Repeat on OFF
Transmission takes place cyclically
when the object value is "OFF".
Repeat on ON and OFF
Transmission takes place cyclically
irrespective of the object value.
Cyclical transmission
Switching object 1.1 ?
yes
No
Here, it is possible to specify whether
cyclical transmission should take place
via the first switching object of the input.
Time for cyclical
transmission
Hours (0...23)
0
...23
If cyclical transmission should take place
via the first switching object of the input,
then the cycle time can be configured
here.
Sets the cycle time hours.
Minutes (0...59)
0
...59
Sets the cycle time minutes.
Seconds (0...59)
0...
30
...59
Sets the cycle time seconds.
Cyclical transmission
Switching object 1.2 ?
yes
no
Here, it is possible to specify whether
cyclical transmission should take place
Page 138 of 143
Software "Rotary sensor with extensions 10FE1x"