Art. No. DS 4092 TS
Figure 38: Example of scene storage
"Only memory function = No":
If a rising or falling edge is detected at the input (according to the configuration), the time
recording operation begins. If actuation ceases during the first second, the appropriate light
scene recall takes place immediately. If the signal length is longer, then the memory telegram is
transmitted after 5 s.
"Only memory function = Yes":
The memory telegram is transmitted immediately after detection of the appropriate signal edge.
Behaviour on bus voltage return for value transmitter and light scene extension
After a device reset (bus voltage return or ETS programming operation), the communication
object of the value transmitter or light scene extension can be initialised. For this, the
"Behaviour on bus voltage return" parameter should be configured to the required reaction. The
setting is dependent on the value transmitter function and edge evaluation selected in the ETS.
In the settings "Reaction as rising edge" or "Reaction as falling edge", telegrams are transmitted
actively to the bus according to the configuration in the ETS. In the "Transmit current input
status" setting, the device evaluates the static signal status of the input and, according to this,
transmits the appropriately configured telegram to the bus (contact closed at the input =
telegram as with rising edge; contact open at input = telegram as with falling edge). This setting
can only be configured with "Transmit value on = rising and falling edge (switch)".
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.
Page 84 of 143
Software "Rotary sensor with extensions 10FE1x"
Functional description