9 Configuration
76
9.4.12 Resistance R
a
,
Here, the starting resistance of the potentiometer
(resistance transmitter) must be entered. I.e. the resis-
tance (between A and S) of the sliding contact at this
position (minimum possible limit stop, e.g. left limit
stop) must be entered.
0 to 10000
Ω
9.4.13 Resistance R
s
The resistance value that the sliding contact can cover
from the minimum value (minimum possible limit stop,
e.g. left limit stop) to the maximum value (maximum
possible limit stop, e.g. right limit stop) must be
entered here.
9.4.14 Resistance R
e
Here, the end resistance value of the potentiometer
(resistance transmitter) must be entered. I.e. the resis-
tance (between E and S) of the sliding contact at this
position (maximum possible limit stop, e.g. right limit
stop) must be entered.
9.4.15 Scaling start
All sensor types can be scaled here if "linear" has been
entered for linearization.
-5000 to 0 to 50000
9.4.16 Scaling end
-5000 to 100 to 50000
9.4.17 Offset
With the offset, the linearized/scaled measured value
can be shifted evenly by the value entered over the
entire measuring range.
-5000 to 0.0 to 50000 °C/°F/
text
Parameter
Comment
Value range
(default setting in bold)
Содержание dTRANS T06 Ex
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 30: ...5 Starting operation of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Starting operation of the device 31...
Страница 67: ...8 IECEx 67...
Страница 106: ...15 Certificates 106 15 Certificates...
Страница 111: ...15 Certificates 111 15 2 SIL and PL...
Страница 112: ...15 Certificates 112 15 3 ATEX...
Страница 113: ...15 Certificates 113...
Страница 114: ...15 Certificates 114...
Страница 121: ......
Страница 122: ......
Страница 123: ......