6 Safety manual
50
6.10 Regular tests
The device test can be carried out as follows:
-
Proof test A: complete test by the manufacturer; the device must be sent to the manufacturer for this purpose.
-
Proof test B: comprehensive test; the device must be removed from the operating facility for this purpose.
-
Proof test C: simplified test; the device can remain in the operating facility for this purpose.
Tests on a device without a sensor can be conducted using corresponding sensor simulators (resistance decade, reference
voltage source, etc.). The accuracy of the measuring devices or multimeter used must meet the device specification.
6.10.1
Proof test A
(corresponds to factory calibration)
For a complete check, the device must be removed from the operating facility and sent to the manufacturer.
v
For service addresses see back cover
6.10.2
Proof test B
With proof test B, the following values for the proof test coverage (PTC) can be achieved:
Voltage supply
Detection of dangerous undetected failures (
λ
DU
)
PTC
DC 24 V +10/-15 %
0.723
72.3 %
Voltage supply
Detection of dangerous undetected failures (
λ
DU
)
PTC
DC 24 V +10/-15 %
0.675
67.5 %
Содержание dTRANS T06 Ex
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 30: ...5 Starting operation of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Starting operation of the device 31...
Страница 67: ...8 IECEx 67...
Страница 106: ...15 Certificates 106 15 Certificates...
Страница 111: ...15 Certificates 111 15 2 SIL and PL...
Страница 112: ...15 Certificates 112 15 3 ATEX...
Страница 113: ...15 Certificates 113...
Страница 114: ...15 Certificates 114...
Страница 121: ......
Страница 122: ......
Страница 123: ......