6 Safety manual
54
6.10.3
Proof test C
With proof test C, the following values for the proof test coverage (PTC) can be achieved:
Voltage supply
Detection of dangerous undetected failures (
λ
DU
)
PTC
DC 24 V +10/-15 %
0.464
46.4 %
Step
Action
Remark
1
Test the current device status of the test piece with the setup program.
Status must be 'OK'
2
If active, deactivate SIL operation of the test piece.
Configure analog output for simulation of current output signal.
Simulate the following output signal values and verify either using down-
stream devices in the operating facility or using a current meter that is ad-
ditionally connected:
Verification of the proper function of the
analog output including whether the er-
ror signal values can be generated.
Simulated value:
Expected measured value:
3.6 mA
3.59 to 3.61 mA
8 mA
7.99 to 8.01 mA
16 mA
15.99 to 16.01 mA
21.2 mA
21.19 to 21.21 mA
3
Reactivate SIL operation.
Disconnect the line of the analog output signal at connection 42(+).
The test piece must signal an error after approx. 5 s.
Verification that, in the event of an inter-
ruption to the output current signal, the
internal test identifies the interruption of
the signal path and signals it.
Содержание dTRANS T06 Ex
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 30: ...5 Starting operation of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Starting operation of the device 31...
Страница 67: ...8 IECEx 67...
Страница 106: ...15 Certificates 106 15 Certificates...
Страница 111: ...15 Certificates 111 15 2 SIL and PL...
Страница 112: ...15 Certificates 112 15 3 ATEX...
Страница 113: ...15 Certificates 113...
Страница 114: ...15 Certificates 114...
Страница 121: ......
Страница 122: ......
Страница 123: ......