9 Configuration
79
9.5.7
Error signal
If, for the measured value, the value is exceeded, not
reached, or a diagnostic error occurs, the current or
voltage value set here is output on the analog output as
a so-called error signal.
v
Chapter 9.5.10 "Behavior when leaving the scal-
Negative signaling,
positive signaling,
replacement value
For signal type 4 to 20 mA
Low 3.6 or high 21.2 mA
For signal type 0 to 20 mA
Low -0.4 or high 21.2 mA
For signal type 2 to 10 V
Low 1.8 or high 10.6 V
For signal type 0 to 10 V
Low -0.2 or high 10.6 V
k
SIL operation
9.5.8
Output simulation
An output current/output voltage can be simulated to
test the system that follows. It is also possible to simu-
late error signals.
OFF
ON
9.5.9
Simulation value
The value set here is simulated. The value range
depends on the signal type that has been set.
for 0(4) to 20 mA;
-0.4(3.6) to 21.2 mA,
for 0(2) to 10 V:
-0.2(1.8) to 10.6 V
k
SIL operation
Parameter
Comment
Value range
(default setting in bold)
Содержание dTRANS T06 Ex
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 30: ...5 Starting operation of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Starting operation of the device 31...
Страница 67: ...8 IECEx 67...
Страница 106: ...15 Certificates 106 15 Certificates...
Страница 111: ...15 Certificates 111 15 2 SIL and PL...
Страница 112: ...15 Certificates 112 15 3 ATEX...
Страница 113: ...15 Certificates 113...
Страница 114: ...15 Certificates 114...
Страница 121: ......
Страница 122: ......
Страница 123: ......