FORM 160.54-O1
33
JOHNSON CONTROLS
2
prograMMaBLe
head pressure setpoint
(15.0 to 60 PSID; default 23.0 PSID)Sets the pressure
differential to which the Control Valve will control the
Head Pressure.
Control Valve output settings - type
(0-10v or 4-20mA; default 0-10v) Sets the output signal
to the Control Valve to be in the form of either 0-10VDC
or 4-20mA.
Control Valve output settings - pid output
(Direct or Reverse) Allows the output signal to the
Control Valve to be set to DIRECT or REVERSE act-
ing. When set to DIRECT, the voltage or current signal
to the Control Valve is at minimum for a 0% command
and at maximum for a 100% command. When set to
REVERSE, the voltage or current signal to the Control
Valve is at maximum for a 0% command and at mini-
mum for a 100% command.
Control Valve output settings - set
(0.0% to 100%; default 0.0%) Allows the Control Valve
to be manually set to a pre-determined position between
0.0% and 100%.
Control Valve output settings - auto
Places the Control Valve in automatic control.
Change setpoints
Use to enter the Head Pressure Control PID variables
below. Pressing this key places a green box around
the first changeable setpoint. Use the up/dn, left/right
arrows to place the selection box aroud thwe desired
setpoint. Wityht the setpoint selected, press the ENTER
(checkmark) key. A dialog box appears with the range
of settings. Using the numeric keys, enter desired value.
Then, press the ENTER (checkmark) key.
head pressure Control - p
Sets the Proportional Gain of the Head Pressure Control
(0.00 to 5.00; default 2.00). Use the Change Setpoints
key as described above to select/enter this setpoint.
head pressure Control – i
Sets the Integral Gain of the Head Pressure Control (0.00
to 5.00; default 2.00). Use the Change Setpoints key as
described above to select/enter this setpoint.
head pressure Control – d
Sets the Derivative Gain of the Head Pressure Control
(0.00 to 5.00; default 0.00). Use the Change Setpoints
key as described above to select/enter this setpoint.
NaVigatioN
home
Causes an instant return to the Home Screen
Condenser
Returns to the Condenser Screen
Содержание YORK YK MaxE
Страница 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...
Страница 183: ...FORM 160 54 O1 183 JOHNSON CONTROLS...