JOHNSON CONTROLS
178
FORM 160.54-O1
fig. 49 –
SAMPLE PRINTOUT (HISTORY)
YORK hiStORY 1
ChilleR id 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 1999 9:23:12 AM
SYSTEM READY TO START
LCSSS – LOGIC BOARD POWER SUPPLY
[List any warnings that were active at the time of
shutdown]
Controls C.MLM.01.06.102
Run Time 0 Days 2 Hr 59 Min
Operating Hours
= 25 Hr
Number Of Starts
= 6
Control Source
= Local
Evaporator
---------------------------------------------------------------------------------
Leaving Chilled Active Setpoint
= 45.0 ~F
Chilled Liquid Pump
= Stop
Chilled Liquid Flow Switch
= Open
Leaving Chilled Liquid Temperature
= 45.0 ~F
Return Chilled Liquid Temperature
= 55.0 ~F
Evaporator Pressure
= 75.0 Psig
Evaporator Saturation Temperature
= 44.4 ~F
Evaporator Refrigerant Temperature
= 44.5 ~F
[If Refrigerant Sensor enabled]
Small Temperature Difference
= 0.5 ~F
Condenser
---------------------------------------------------------------------------------
Condenser Liquid Pump
= Stop
Condenser Liquid Flow Switch
= Open
Leaving Condenser Liquid Temperature
= 95.0 ~F
Return Condenser Liquid Temperature
= 85.0 ~F
Condenser Pressure
= 200.0 Psig
Condenser Saturation Temperature
= 101.4 ~F
Small Temperature Difference
= 6.4 ~F
Drop Leg Refrigerant Temperature
= 83.0 ~F
[If Drop Leg Sensor enabled]
Sub Cooling Temperature
= 18.4 ~F
[If Drop Leg Sensor enabled]
Compressor
---------------------------------------------------------------------------------
Discharge Temperature
= 120.0 ~F
Liquid Line Solenoid
= Off
[If Mod C Chiller]
Vent Line Solenoid
= Off
[If Mod D Chiller or higher]
Oil Sump
---------------------------------------------------------------------------------
Oil Pump Run Output
= Off
Sump Oil Pressure (LOP)
= 75.8 Psig
Pump Oil Pressure (HOP)
= 76.6 Psig
Oil Pressure
= 0.0 Psid
Oil Sump Temperature
= 150.0 ~F
Oil Heater
= Off
[If Mod D Chiller or higher]
Oil Return Solenoid
= Off
[If Mod D Chiller or higher]
[Skip the following section if Hot Gas Bypass is not
enabled]
Hot Gas
---------------------------------------------------------------------------------
Valve Position
= 0 %
Pre-Rotation Vanes Position
= 0 %
Surge
---------------------------------------------------------------------------------
Total Surge Count
= 127
Surge Window Time
= 1 Min
Surge Window Count
= 0
[Skip the following section if Variable Speed Oil Pump
is not installed]
Variable Speed Oil Pump
---------------------------------------------------------------------------------
Oil Pump Drive Command Frequency
= 25.0 Hz
Pulldown Time Remaining
= 9.0 Min
[If Pulldown in effect]
[Skip the following section if Liquid Level is not
enabled]
Refrigerant Level Control
---------------------------------------------------------------------------------
Refrigerant Level Position
= 35 %
Ramp Up Time Remaining
= 15 Sec
[If Ramp Up in effect]
Proximity Probe
---------------------------------------------------------------------------------
High Speed Thrust Bearing Proximity Differen = 2 Mils
High Speed Thrust Solenoid
= Off
[If Mod C Chiller]
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
---------------------------------------------------------------------------------
Motor Run
= Off
% Full Load Amps
= 0 %
[Skip the following section if Motor Type is not Mod A
SSS]
Liquid-Cooled Solid State Starter
---------------------------------------------------------------------------------
Motor Run
= Off
% Full Load Amps
= 0 %
Phase A Voltage
= 447 V
Phase B Voltage
= 409 V
Phase C Voltage
= 442 V
Phase A Current
= 0 A
Phase B Current
= 0 A
Phase C Current
= 0 A
[Skip the following section if Motor Type is not Mod B
SSS]
Liquid-Cooled Solid State Starter
---------------------------------------------------------------------------------
Starter Model
= 26L
Motor Run
= Off
% Full Load Amps
= 0 %
kW Hours
= 20723 kWH
printers
Содержание YORK YK MaxE
Страница 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...
Страница 183: ...FORM 160 54 O1 183 JOHNSON CONTROLS...