FORM 160.54-O1
Pre-Run
Access Level Required
: SERVICE
Allows Service Technician to select either Standard (30
seconds) or Extended (180 seconds)
Oil Pump Package
Access level Required
: SERVICE
Allows Service Technician to enter the applied oil pump
drive type as either Variable Speed or Fixed Speed.
Service Technicians refer to YORK Service Manual
160.54-M1.
Motor Communications Protocol
(VSD applications – Software version C.OPT.01.16.307
or later)
(Style B Liquid Cooled Solid State Starter applications
– Software version C.OPT.01.18.307 or later)
Access Level Required:
SERVICE
Only displayed when MOTOR DRIVE TYPE setpoint
above is selected as “VSD-60Hz”, “VSD-50Hz” or
“SSS-Mod B”. Allows the Service Technician to en-
able the appropriate serial communications port for
communications with the Style B Liquid Cooled Solid
State Starter (LCSSS) or Variable Speed Drive (VSD).
Entered as “York” to enable COM 5 (J15) or “Modbus”
to enable COM 2 (J13). Selection required is based on
hardware and interface that is present. Service Techni-
cians should refer to York Service Manual 160.54-M1
Section 11 (LCSSS) or Section 12 (VSD) to determine
which hardware/interface is present. This setpoint and
entry instructions are described in detail in Section 3A
and 23 of Service Manual 160.54-M1. The chiller must
be stopped with the Start-Run-Stop/Reset switch in the
Stop/Reset position to change this setpoint.
Motor node ID
(VSD applications – Software version C.OPT.01.16.307
or later) (Style B Liquid Cooled Solid State Starter appli-
cations – Software version C.OPT.01.18.307 or later)
Access Level Required:
SERVICE
Only displayed when “Modbus” is selected for the Mo-
tor Communications Protocol setpoint above. Allows
the Service Technician to enter the Modbus Address of
the VSD Logic Board or Style B LCSSS Logic/Trigger
Board. The Motor Node ID setpoint must be set to “1”
to match the address assigned to the VSD Logic Board
or Style B LCSSS Logic/Trigger Board. This setpoint
and entry instructions are described in detail in Section
3A and 23 of Service Manual 160.54-M1. The chiller
must be stopped with the Start-Run-Stop/Reset switch
in the Stop/Reset position to change this setpoint.
VSD applications: Set the Modbus Address of VSD
Logic Board 031-02506 to “1” by setting Switch SW3
position 1 to “ON with all other positions “OFF”.
Style B Solid State Starter applications: Set the Modbus
Address of the Logic/Trigger Board 031-02505 to “1”
by setting Switch SW1 position 1 to “ON” with all other
positions “OFF”.
Coastdown Time
(Software version C.OPT.01.16.xxx (or later))
Access Level Required
: SERVICE
Only displayed when “Standard” is selected as the
COASTDOWN Setpoint above. Allows Service techni-
cian to select appropriate coastdown time for compressor
motor applied. Larger motors require a longer coastdown
time to assure the motor rotation has stopped before
the oil pump is turned off at completion of post-lube.
Programmable range is determined by the CHILLER
STYLE/COMPRESSOR setpoint (Style F/J7 and G/K6-
K7, the range is 240 (default) to 900 seconds. All others,
the range is 150 (default) to 900 seconds). Service Tech-
nicians refer to YORK Service Manual 160.54-M1.
Condenser Temperature Range
(Software version C.OPT.01.19.307 or later)
Access Level Required:
ADMIN
Special order R134a chillers are allowed to operate at
higher than standard condenser temperatures. The result-
ing higher operating pressures require higher condenser
warning and safety shutdown thresholds than standard
applications. These chillers are equipped with a special
High Pressure Cutout Switch (HPCO) that can be set to
trip at a higher pressure.
This setpoint allows for either standard or higher tem-
perature condenser temperature operation. It is set at the
factory and requires an ADMIN password to change it. It
is only visible when set to “Extended”. It is set to “Ex-
tended” for those chillers equipped for high condenser
temperature operation. Otherwise, it is set to “Standard”.
For R134a chillers, the thresholds are as follows:
optiView Control Center
Содержание YORK YK MaxE
Страница 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...
Страница 183: ...FORM 160 54 O1 183 JOHNSON CONTROLS...