JOHNSON CONTROLS
104
FORM 160.54-O1
Motor Current Limit
Access Level Required
: OPERATOR
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the motor
current reaches this value, the pre-rotation vanes will
not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close
to reduce the current to this value.
Pulldown Demand Limit
Access Level Required
: OPERATOR
Allows the user to specify the current limit value (as
a percentage of Full Load Amps) to which the chiller
will be limited during the specified pulldown limit time.
This value will override the Motor Current Limit value
during this time period. This function is used to provide
energy savings following chiller start-up.
Pulldown Demand Time
Access Level Required
: OPERATOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chiller
starts.
Access Level Required:
VIEW
Generates
Setpoints
print report.
NaVigatioN
Home
Access Level Required
: VIEW
Causes an instant return to the Home Screen.
Setup
Access Level Required
: VIEW
Moves to the sub-screen allowing setup of general
system parameters.
Quick Start
(Software version C.OPT.01.21.307 and later)
Access Level Required:
ADMIN (to initially enable the feature);
SERVICE (if feature is enabled)
Moves to the sub-screen allowing the Quick Start feature
to be enabled/disabled. Once enabled, this screen allows
programming and viewing of Quick Start setpoints and
parameters.
optiView Control Center
Содержание YORK YK MaxE
Страница 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...
Страница 183: ...FORM 160 54 O1 183 JOHNSON CONTROLS...