VariaBLe speed driVe (Vsd) detaiLs sCreeN
(stYLe d Vsd aNd Vsd With part NUMBer 371-03789-xxx (503 hp 60 hz; 410hp 50
hz))
oVerVieW
This screen displays more detailed information pertain-
ing to a Variable Speed Drive (VSD). Flash memory
Card version C.MLM.01.08.xxx and later is required
for VSD part number 371-03789-xxx (503HP 60Hz;
419HP 50Hz)
.
Service Technicians refer to YORK
Service Manual 160.54-M1 for operation instructions
and explanation of all programmable setpoints and
displayed values.
dispLaY oNLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the Variable Speed Drive
this is the data returned by the VSD Logic board.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC
input in Analog Remote mode, PWM signal in Digital
Remote mode, MicroGateway interface in ISN mode,
or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Water Pump Output (LED)
Indicates whether the relay controlling the water pump
output is energized.
Precharge Relay Output (LED)
Indicates whether the relay controlling the precharge
output is energized.
Trigger SCR Output (LED)
Indicates whether the relay controlling the trigger SCR
output is energized.
DC Bus Voltage
Displays the DC Bus voltage as reported by the VSD.
DC Inverter Link Current
Displays the DC Inverter link current as reported by
the VSD.
Internal Ambient Temperature
Displays the ambient temperature inside the VSD cab-
inet as reported by the VSD.
Converter Heatsink Temperature
Displays the heatsink temperature of the converter as
reported by the VSD.
LD09096
fig. 20
optiView Control Center
Содержание YORK YK MaxE
Страница 10: ...JOHNSON CONTROLS 10 FORM 160 54 O1 OptiView Control Center THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 17: ...FORM 160 54 O1 17 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 54 O1 59 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 65: ...FORM 160 54 O1 65 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 79: ...FORM 160 54 O1 79 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 54 O1 91 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...FORM 160 54 O1 105 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 54 O1 113 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 123: ...FORM 160 54 O1 123 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...FORM 160 54 O1 133 JOHNSON CONTROLS 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...JOHNSON CONTROLS 166 FORM 160 54 O1 Printers...
Страница 183: ...FORM 160 54 O1 183 JOHNSON CONTROLS...