Creating a trigger and alarm sound in EntraPass
1.
On the EntraPass main menu, click the
Devices
tab and click
Controller
.
2.
From the
Controller
list, select the controller.
3.
Click the
Trigger and Alarm
tab.
4.
Right-click and select
New trigger
.
5.
In the
Trigger and Alarm
window, in the
English
field, enter a name for the trigger.
6.
On the
General
tab, from the
Component Type
list, select
Controller
.
7.
From the
Controller
list, select the controller.
8.
From the
Trigger schedule
list, select
Always valid
.
9.
On the
Events
tab, click
Controller communication failed
.
10. On the
Alarm notification
tab, from the
Alarm schedule
list, select
Always valid
.
11. From the
Desktop alarm
list, select
Always valid
, and click the
Save
icon.
12. On the EntraPass main menu, click the
Options
tab and click
Multimedia Device
.
13. On the
Sound
tab, from the
Priority
list, select the priority level associated with the
event
Controller communication failed
. The default is priority level 3.
14. Click
Assign alarm sound
and select an alarm sound from the list.
15. Click
OK
.
16. On the EntraPass main menu, click the
Desktops
tab, right-click one of the eight
desktop views and select
Properties
.
17. In the
Desktop properties
window, in the
Alarms Desktop
pane, select
Messages
screen
and click
OK
.
When a controller's communication fails, a message displays in the desktop view and an
alarm sounds.
Endurance: level IV (100,000 cycles)
Standby power: Level 1 (when no standby power is provided) and level IV (4 hours, when using KT-
PS485)
Note:
If KT-1 is used in a single gang configuration, powered by an external, separately
listed power supply or PoE/PoE+ switch the performance levels remain the same with the
exception of the standby time that will be rated Level I (no secondary power source).
To comply with UL listings, the following requirements must be met:
•
Installation locations and wiring methods shall be in accordance with the National Electrical
Code, ANSI/NFPA 70.
•
Do not connect to a receptacle controlled by a switch.
•
Use of a UL listed computer.
•
Use of UL listed readers (Wiegand 26 and 34 bits, stripe 26 and 34 bits, XSF 39 bits have been
tested and found to comply).
•
Kantech XSF 39 bits have been tested and found to comply.
•
Use of a UL recognized tamper switch on every housing cabinet for the KT-1 One-Door
Controller.
•
Do not use the SmartLink option.
•
Do not use a 230 VAC transformer (not UL listed).
•
Use only UL listed cables.
•
Use only UL listed adaptors.
•
Use only a UL listed power supply such as Kantech part number KT-PS4085 (available
through Kantech distributors or dealers, please refer to the Technical Support contact
information at the beginning of this guide to obtain the specific transformer).
•
The KT-1-EU has not been validated as a UL Listed system.
•
The PTC1640UG and 12V/7Ah battery are used for 4 hours of standby power.
•
Security hardening guide has not been evaluated by UL.
•
KT-MOD-IO16 has not been evaluated by UL.
Note:
All circuits are power limited with the exception of battery connection. Separation of
3/4 in. shall be maintained between power limited and non-power limited wiring.
Note:
Replace battery with Changzhou Jintan Chaochuang Battery Co Ltd., Pansonic
or Energizer Part No. CR2032 Only. Use of another battery may present a risk of fire or
explosion.
KT-1 One-Door Controller Installation Guide
51
Содержание Tyco KT-1
Страница 1: ...KT 1 One Door Controller Installation Guide D29008966R009 2021 03 08 DN2186 2103 ...
Страница 2: ......
Страница 8: ......
Страница 24: ...Figure 5 KT 1 PCB inputs and outputs 22 KT 1 One Door Controller Installation Guide ...
Страница 26: ...Figure 6 KT 1 controller with KT PS4085 power supply 24 KT 1 One Door Controller Installation Guide ...
Страница 29: ...Figure 8 KT 1 PCB EU inputs and outputs KT 1 One Door Controller Installation Guide 27 ...
Страница 56: ...KT 1 One Door Controller Installation Guide 54 ...