Callout
Description
E
Door locking device: 12 VDC 750 mA maximum
F
Connect a 1000 Ohm resistor between LK- and +12V if you are not using a locking
device.
G
Door contact
H
Optional end of line resistor
I
Request to exit device
J
Individually programmable zone termination: NC, NO, NEOL, single or double EOL
termination.
K
Connect the RS-485 main network to other KT-1 controllers or to the gateway using
a USB-485 interface.
L
Earth ground connection
M
Optional exit reader
N
Extra outputs used as a general annunciator
O
Battery: 12 V 7A/H
P
AC power: 230 VAC 50 Hz
Q
Power supply case screw
R
Power supply (approved type):
In: 230 VAC 50 Hz
Out: 13.8 VDC 1.5A
26