equipment is installed in a metallic cabinet that meets the applicable requirements for a FIRE
ENCLOSURE.
Note:
When installed on the North American Market, powered via the UL, cUL Listed 40VA
Transformer, the KT-1 shall be connected to the mains by a LICENSED ELECTRICIAN in
accordance with the applicable rules of the National Electrical Code or Canadian Electrical
Code regarding this type of connection.
1.
The connection to the mains supply must be made as per the local authorities rules and
regulations. An appropriate disconnect device must be provided as part of the building
installation. Where it is not possible to rely on the identification of the NEUTRAL in the AC
MAINS SUPPLY, the disconnecting device must disconnect both poles simultaneously (LINE
and NEUTRAL).
2.
AVOID setting up the equipment near heaters, air conditioners, ventilators, and/or
refrigerators; DO NOT select a place that exposes your controller to direct sunlight, excessive
heat, moisture, vapors, chemicals or dust.
3.
If during the installation a knockout on the cabinet is removed, it is the installer's
responsibility to ensure that the same degree of protection for the cabinet is provided by the
use of bushings, fittings, adequate sealant, etc.
4.
If a metallic cabinet is used, the cabinet must be secured to the building structure before
operation. Use four (4) stainless steel tapping screws #8, 32 mm (1.25 in.) to mount the
cabinet.
5.
The ground connection must be as shown within the included diagram, or equivalent.
6.
Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation;
- Reducing the clearance between SELV (Safety Extra Low Voltage) circuits and NON-
POWER Limited Circuits (Battery wires);
- Route the battery wires away from the rest of the SELV circuits.
7.
It is the end-user and/or installer's responsibility to ensure that the disposal of the used
batteries is made according to the waste recovery and recycling regulations applicable to the
intended market.
8.
There are no serviceable parts within the equipment; For any issues regarding the
equipment please contact your installer.
9.
Before leaving the premises, the Ethernet communication lines must first be connected
to an approved (acceptable to local authorities) type Network Interface Device (NID), (UL
installations, UL 60950 listed NID, or UL 62368-1, for ULC installations CAN/CSA C22.2, No.
60950-1 or No. 62368-1 Certified NID). All wiring shall be performed according to the local
electrical codes.
10. DISCONNECT POWER BEFORE SERVICING.
11. DO NOT OPEN the enclosure! Hazardous voltages may become accessible!
KT-1 One-Door Controller Installation Guide
11
Содержание Tyco KT-1
Страница 1: ...KT 1 One Door Controller Installation Guide D29008966R009 2021 03 08 DN2186 2103 ...
Страница 2: ......
Страница 8: ......
Страница 24: ...Figure 5 KT 1 PCB inputs and outputs 22 KT 1 One Door Controller Installation Guide ...
Страница 26: ...Figure 6 KT 1 controller with KT PS4085 power supply 24 KT 1 One Door Controller Installation Guide ...
Страница 29: ...Figure 8 KT 1 PCB EU inputs and outputs KT 1 One Door Controller Installation Guide 27 ...
Страница 56: ...KT 1 One Door Controller Installation Guide 54 ...