Subject to change without notice!
User Manual ECOSTEP®54
35
7.3.1
Error case
If an error occurs the red „ERR“ LED goes on and in the status word (menu „Separate Axis DS402 - Device
Profi le DS402 - Ax -> Device State Control“) the „Fault“ bit is set.
Fig. 7.11: „Device State Control“ window with bit by bit representation of the control and status word
Fault conditions are evaluated individually for each axis and displayed in the „Device Profi le -> Error Flags“
window (Shortcut F2):
Fig. 7.12: Display of the Error Flags (F2)
Table 7.8: Error states in the „Error Flags“ window
Name
Error Description
Measures
FAULT_H8SWD_BIT
Internal controller error
Try to reset the fault condition (cf. page 36).
If no success, replace device
FAULT_REGLERWD_BIT
Internal controller error
Replace device
FAULT_OVERTEMP_BIT
Heat sink temperature too high (> 80 °C)
Switch off device. Check heat dissipation.
FAULT_UVMESS_BIT
Power supply voltage too low (< 15 V)
Check voltage
FAULT_ABORT_CONN_
BIT
Bus error
Check bus connection and device function