5.1.3
Assembly
When mounting the ECOSTEP®54 into the cabinet cable clamps (contained in connector kit AMK40, cf.
chap. 8) assure that the connecting cables are laid EMC conform by connecting the cable shield extensively
to chassis earth. Maximum cable diameter is 15 mm.
It is important that the air fl ow is not disturbed by components above or below the stepper motor ampli-
fi ers.
If a heat sink is used (cf. chap. 8.1.1), the mounting space will increase by 40 mm.
Th e surface of the mounting plate has to be conductive (e.g. zinc plated). Varnished mounting plates must
not be used.
To calculate the minimal mounting depth (fi g. 5.3, dim A) the form of the connectors (cable outlet direction)
and the minimum bending radii of the connecting cables at the sub-D connectors have to be regarded.
Fig. 5.3: Mounting dimensions cabinet, width and depth [mm]
24
0
105
65
65
30
30
Cable conduct
Cable conduct
Mounting plate
with conductive
surface
Cubicle door
A
170
Cylindric screw
M5 DIN912