background image

JA-14K(R) Security System Control Panel 

36 / 72 

MNX22101

 

 

UNSET 

(control of the 

whole system) 

 

Authorization:

 

All 

JA-10:  

Status: 

Section 1: Unset; 

Section 2: Unset; 

Section 3: Unset; 

Section 4: Unset, Error; 

GSM: 90%; 

Time 17:01 22.7. 

Installation name according to the Communication tab 

Status: 

Name and status of Section 1 

Name and status of Section 2 

Name and status of Section 3 

Name and status of Section 4 

GSM signal quality 

Time and date of sending the SMS to the GSM network 

 

SET 1 3 

 

(control of 

selected system 

sections) 

 

Authorization:

 

All 

JA-10:  

Status: 

Section 1: Set; 

Section 3: Set with an active zone; 

GSM: 90%; 

Time 17:01 22.7. 

Installation name according to the Communication tab 

Status: 

Name and status of Section 1 

Name and status of Section 3 

GSM signal quality 

Time and date of sending the SMS to GSM 

 

UNSET 2 4  

(control of 

selected system 

sections) 

Authorization:

 

All   

JA-10:  

Status: 

Section 2: Unset; 

Section 4: Unset; 

GSM: 90%; 

Time 17:01 22.7. 

Installation name according to the Communication tab 

Status: 

Name and status of Section 2 

Name and status of Section 4 

GSM signal quality 

Time and date of sending the SMS to GSM 

CREDIT 

(checking the 

credit balance 

on the pre-paid 

SIM card) 

Authorization: 

All 

JA-10: 

… 

… 

… 

Time 17:01 22.7. 

Installation name according to the Communication tab 

Text from GSM provider response 

Text from GSM provider response 

Text from GSM provider response 

Time and date of sending the SMS to GSM 

9.8 Controlling the system via N-Link 

N-Link SW is used for local and remote programming of the whole system or user editing; provide an overview 

of section statuses and section control. Control is possible by clicking on the “Section” tab in the “status” column 

or also by clicking on the number of the section on the lower status bar. The system records system control to 

its event memory according to authorization upon user authorization in the software. 

 

 

9.9 Control by Duress access control 

This option, switched off by factory default, enables users to control (set or unset) the system with a different 

code when they are threatened by another person. This code will unobtrusively draw attention to such  

a situation by triggering a silent Panic alarm without any acoustic or visual indication. A panic alarm is triggered 

by adding 1 to an existing user code.  

Example:  

User code = 4444. Duress access control code = 444

Warning:

 If the user code ends with the number 9 when using Duress access control, then the last number of 

the code will be 

0. 

Содержание JA-10 Series

Страница 1: ...requirements The control panel has BUS and or wireless device when the control panel is equipped with a radio module compatibility It is recommended that only JA 10 devices are used with the system P...

Страница 2: ...Installation of wireless devices enrollment mode 17 7 Switching the system ON 18 8 System configuration 18 8 1 The system profiles 18 8 2 Control panel operation modes 22 8 3 Authorisation of users 22...

Страница 3: ...ements for the setup of transmission paths to an ARC 59 10 11 2 Transmission paths 59 10 11 3 JA 10 CID and SIA codes 60 10 11 4 Setting the transmission of photos to external storage 61 11 Other N Li...

Страница 4: ...A Panic alarm is triggered during system control when a code is entered with 1 mathematically added to the last digit s value Caution enabling this function erases all predefined codes in the system D...

Страница 5: ...ed the system triggers a Fault Intrusion detectors a group of detectors designed to identify the intruder It includes detectors of motion or opening If they have set reactions for releasing a delayed...

Страница 6: ...ing a USB cable two drives will be displayed in the File Manager FLEXI_CFG and FLEXI_LOG The capacity of supplied card can be 4GB SD SD HC or it can be higher Before you use brand new SD card perform...

Страница 7: ...ath properties to the ARC are mentioned in the chapter on communicator settings NOTE 2 The term communication path is meant as a physical transmission medium for instance metallic cables optical fibre...

Страница 8: ...een used in the system Only system Administrator s is are fully responsible for editing already existing user codes and assigning new codes 1 2 2 Security access codes and RFID devices The control pan...

Страница 9: ...Device type Description Who does the action Frequency of the action Fire detectors Test of functions inform the ARC agency before you proceed Administrator Once per month Clean up the dust and dirt Ad...

Страница 10: ...herwise is unset Note The cleaning lady user with access to the whole premises common section can have only a virtual section assigned 1st level and it does not have to include any detectors Unsetting...

Страница 11: ...nnector is only used to connect the radio module directly in the control panel Maximum BUS cable length 500 m 3 1 Description of JA 14K R control panel The JA 14K R control panel is designed for small...

Страница 12: ...0 mA fuse 6 Tamper contact of the housing 7 JA 111R radio module 8 USB connector for PC connection 1 Connector for supplementary modules GSM or PSTN communicator 2 MicroSD card holder 3 LED indicators...

Страница 13: ...meant to be used for connecting a supplementary communicator Also an RJ connector RJ 44 is placed on the control panel PCB and serves for the connection of the JA 111R radio module if installed insid...

Страница 14: ...it also functions as a main switch Caution Don t connect any other electrical appliance to this specific circuit not even power for external PG outputs or a heating system or any other device related...

Страница 15: ...sum of the length of all the cables between all the connected devices The number of connected BUS devices is limited by the capacity of the backup battery of the control panel To meet the standard fo...

Страница 16: ...4K control panel for 2 6 Ah battery calculation is valid for 80 of battery capacity 2 6 Ah 0 8 12 h 0 17 A according to the capacity maximum current for 12 hrs Imax 0 17 A 0 05 A 0 12 A subtract the c...

Страница 17: ...Thus it may happen that signals from the same unidirectional device may exhibit quite different data in N Link System settings Diagnostics during repeated measurements depending on from which module...

Страница 18: ...m configuration of the keypads 9 Set the required functions and test the system see chapter 10 7 Parameters tab 8 System configuration The security system protected premises building can be split into...

Страница 19: ...l Period of waiting for alarm confirmation 10 1 60 min Control panel Waits for confirmation of fire of another detector 10 1 60 min Control panel Delayed report to ARC NO NO Control panel Ways of sett...

Страница 20: ...40 5 900 s Control panel Entrance delay 30 5 30 s Control panel Exit delay 30 5 60 s Control panel Entrance delay by garage door 30 5 30 s Control panel Exit delay by garage door 60 5 60 s Control pan...

Страница 21: ...1 1 Grade 2 Passable Impassable Passable Impassable Active tamper X X Active input any input Active instant input X X Active alarm memory indication X RF device 20 min no response X Siren fault X Faul...

Страница 22: ...amper alarm Unset mode is indicated on the keypad by a green light on the specific status indicator letters A D and indication button SET fully or partially All detectors are active and guard except I...

Страница 23: ...ns selected by the main Administrator to which the other Administrator can add new users with the same or lower level of authorization to control sections and PG outputs assign them with access codes...

Страница 24: ...n only be unlocked by the manufacturer Reset of the control panel is described in chapter 12 Reset of the control panel Report unset section System reports about an unset section when there is no move...

Страница 25: ...r click Ctrl you can delete all of them or you can just change a common parameter Caution It is recommended to enroll wireless devices to the system according to point B in real conditions and at the...

Страница 26: ...low Delay confirmed Intrusion alarm with an entry and exit delay see the chapter Confirmed intrusion reaction Tamper alarm Tamper alarm any time the section does not need to be set 24 hours Immediate...

Страница 27: ...ee activations on the fourth intrusion a bypass is activated for the respective alarm input and the corresponding sensor is excluded from further activity If these three activations occur during an al...

Страница 28: ...regardless of the system status set unset Most devices have a built in tamper contact for the detection of opening their cover and tearing from the wall An activation triggers a tamper alarm and it is...

Страница 29: ...s which ensure permanent protection supervision of their health regardless of the system status set or unset can have a pre set reaction of 24 hours or flooding This type of alarm is assigned to the g...

Страница 30: ...ctions and PG outputs PG outputs can be blocked N Link software PC with Windows USB cable Sections can be controlled and also PG outputs after authorization Voice menu Telephone Supplementary GSM or P...

Страница 31: ...orization is always required so in the event log it is recorded who unset the system The setting procedure 1 Full section setting before you leave the protected premises no one else in the premises A...

Страница 32: ...tion to cancel the alarm memory or using the LCD keypad menu and selecting the option Cancel warning indication 9 3 System control by remote control If there is a requirement to control the system bef...

Страница 33: ...set immediately in the pre set time The option is for fast and silent setting with no warning The control panel fully respects all ways of setting and checking the systems ready to be set rules Set a...

Страница 34: ...pecial reports Control of PG outputs is not possible via the voice menu Caution Makes sure nobody is present in the protected premises before you set the system remotely 9 7 SMS commands The system ca...

Страница 35: ...on 3 Name and status of Section 4 GSM signal quality Time and date of sending the SMS to the GSM network COM info about communication Authorization Service JA 10 GSM 90 DATA ok CELLID 44905 OPID 23003...

Страница 36: ...g the credit balance on the pre paid SIM card Authorization All JA 10 Time 17 01 22 7 Installation name according to the Communication tab Text from GSM provider response Text from GSM provider respon...

Страница 37: ...ller calendar N Link Web and smart app Set always Will set always despite faults or triggered devices status Will set always despite faults or triggered devices status Will set always despite faults o...

Страница 38: ...call 2 6 Instant alarm SMS alerts 1 Alarm call 2 7 Instant alarm cancelled SMS alerts 1 Alarm call 2 8 Delay alarm SMS alerts 1 Alarm call 2 9 Delay alarm cancelled SMS alerts 1 Alarm call 2 10 Tampe...

Страница 39: ...ection or switching on a PG Two long beeps Functional button deactivation unsetting a section or switching off a PG Two long repeated beeps Unsuccessful setting Three long beeps Section unsetting with...

Страница 40: ...for access control blocking the heating when a window is open or when a section is set garden watering etc i e home automation 10 Setting the system through N Link SW The JA 10 system is exclusively p...

Страница 41: ...quested languages and complete the selection with Send g Make note of the Activation Code displayed in green and enter it in N Link The list of generated Activation Codes will remain saved at the webs...

Страница 42: ...tomatically get into the Service mode If the control panel has been configured before its service code has been changed the software will request entry of the code it should be entered in the format n...

Страница 43: ...nctional button is blocked it is indicated by yellow colour it cannot shows all its sections are fully set or unset Status indicates the current status of a section Unset Set Exit Delay Entrance Delay...

Страница 44: ...battery in the device or control panel BOOT upgrading of the device is going on or upgrade failure repeat upgrade By moving the mouse cursor on the device STATUS you will display detailed data Note i...

Страница 45: ...f a detector or internal status if there is a request from two devices the OR logic is used Time setting of time for the functions Impulse Time is set in the format hh mm ss in the range of 00 00 01 t...

Страница 46: ...control panel the output will not be activated By a device enables activation of a PG output by a device detector activation pressing a tag etc The setting is linked to the Devices tab One device may...

Страница 47: ...ir phones The groups and the SMS format are described in the attached table To make changes in this tab you do not need to be in the Service mode User enables selection of a user from the list of user...

Страница 48: ...fer certain events to be reported typically reports of failures and restoration of power supply or possibly setting with an active device only for selected users administrator etc User defined SMS 2 s...

Страница 49: ...communication is set to Without remote programming factory default setting Siren IW when partially set Allows you to set an acoustic alarm with the IW system if the section is partially set Fire and...

Страница 50: ...he history It is recorded in the system history and also reported by a supplementary GSM or PSTN module if connected by an SMS to a pre set user if the event SMS about unsuccessful setting is enabled...

Страница 51: ...hen enabled an Internal alarm will be triggered after the entrance delay has timed out but the system waits for 15 s to send an alarm report to the ARC A user has 15 s more to unset the system without...

Страница 52: ...f the device contains a battery its status is displayed For the control panel position 0 the voltage of the backup battery is displayed If the voltage data of a wireless device are missing the device...

Страница 53: ...are offered here their activation allows blocking a calendar action Blocked possibility to block a particular action Disabling is indicated by a red dot The Service Technician using N Link is authori...

Страница 54: ...S about unsuccessful setting If enabled the control panel sends an SMS about unsuccessful setting When controlling is performed by an authorized user then the control panel sends an SMS to the telepho...

Страница 55: ...ith GSM signal quality you are recommended to test a SIM card of another operator You are not recommended to use a directional or gain GSM antenna for the communicator it only reduces connection of th...

Страница 56: ...her settings registration to the MyJABLOTRON web service must be performed by the ARC technician once again Sensitivity of DTMF detection from ARC setting the sensitivity of reception of the signal ge...

Страница 57: ...caller ID service CLIP activated Generated DTMF level for ARC setting the intensity of the transmitted tone dialling signal in DTMF generated by the control panel The intensity is adjustable in 10 st...

Страница 58: ...able options are visible The Automatic option uses a combination of LAN GSM communicators which primarily uses LAN and in a case of unavailable LAN switches to backup GSM In case of failure of transmi...

Страница 59: ...t Encryption System time Event time SP2 PSTN GSM LAN JABLO IP SIA IP SIA CID Optional 1 per 24 hrs 120 s 2 30 s Optional Required Required SP3 GSM LAN JABLO IP SIA IP SIA CID Not allowed 1 30 min 60 s...

Страница 60: ...T Low Battery in device Faults and service events 1401 OP Unset Setting Unsetting 1402 OG Unset partially Setting Unsetting 1406 BC Alarm cancelled by user Burglary 1407 OQ Unset remotely Setting Unse...

Страница 61: ...tially set Setting Unsetting 3407 CQ Set remotely Setting Unsetting 3412 LE Remote access closed Uncategorised 3417 CU Remotely partially armed Setting Unsetting 3570 EU End of device bypass deactivat...

Страница 62: ...istory Event history is accessible in N Link by pressing of the Events button and selecting Event history In the memory of the control panel microSD card up to several millions of records may be store...

Страница 63: ...ver recorded in the history arranged by date and time and also all setting changes 5 You can import settings from another installation to the system e g after replacing an old control panel with a new...

Страница 64: ...rol panel mode between the Unset status when changes of setting can be done in all tabs except the Settings tab and the Service mode changes can be done in the Devices tab incl enrolling changes of in...

Страница 65: ...lation information The window contains items for the installation company to save important contact information about the system owner the entire system and possibly an external document related to th...

Страница 66: ...anel does not cause deletion of the history of events saved on the memory SD card If Reset was not executed correctly the control panel will keep the original settings without changes 13 Firmware upda...

Страница 67: ...ffer the possibility of re importing the original settings 9 Perform a check in accordance with the description in chapter Check after a FW change 13 4 Check after a FW check 13 3 FW updates for wirel...

Страница 68: ...o window during generation of the Info window the control panel addresses all connected devices and wireless devices to ask for their current information The Info window offers a general overview of t...

Страница 69: ...ss connection 25 mA 25 mA JA 10A Internal siren 5 mA 30 mA during an alarm JA 11A External siren 5 mA 50 mA in case of an AC supply failure without battery charging otherwise 550 mA depending on batte...

Страница 70: ...3 Explain what authorization is what it is for and options like codes RFID tags etc 4 Partial setting at home Difference in indication between partial and full setting 5 Control of home automation usi...

Страница 71: ...ons 4 Max number of users 16 Max number of PG outputs 4 Alarm connection JA 10 BUS dedicated wiring Wireless connection with JA 111R unspecified wireless connection JA 10 wireless protocol Alarm syste...

Страница 72: ...2 R module EMC EN 50130 4 EN 55022 ETSI EN 301 489 7 ETSI EN 301 489 3 Electric safety EN 60950 1 Operational conditions ERC REC 70 03 ERC DEC 98 20 Certification body TREZOR TEST JABLOTRON ALARMS a s...

Отзывы: