JA-14K(R) Security System Control Panel
20 / 72
MNX22101
System parameter overview when “EN 50131-1, grade 2”, is set:
Device
Parameter
Option
Blocking
(limitation)
Control panel
Siren when partialy set
NO
NO
Control panel
Sirens enabled
YES
YES
Control panel
Administrator – restricted Service/ARC rights
YES
YES
Control panel
Service and ARC controls the system
NO
YES
Control panel
Duress access control
YES
NO
Control panel
Alarm confirmation within one section
NO
NO
Control panel
Siren (IW output) when a tamper is triggered
YES
YES
Control panel
Reset enabled
NO
YES
Control panel
Report unset section
NO
NO
Control panel
Unsuccessful setting
YES
YES
Control panel
Alarm memory indication
NO
YES
Control panel
Alarm length
240
5…900 s
Control panel
Entrance delay
30
5…30 s
Control panel
Exit delay
30
5..60 s
Control panel
Entrance delay by garage door
30
5…30 s
Control panel
Exit delay by garage door
60
5…60 s
Control panel
Period of waiting for alarm confirmation
10
1…60 min
Control panel
Waits for confirmation of fire of another detector
10
1…60 min
Control panel
Delayed report to ARC
YES
NO
Control panel
Ways of setting
According to profile
YES
Control panel
Authorization type
Standard
NO
Control panel
Supervision of wireless devices
YES
NO
Radio module
RF jamming detection
Low
NO
Keypad
Optical indication setting
2.Section status
change (BUS) or
4.Functional button
status change
YES
Keypad
Alarm acoustic indication
YES
YES
Keypad
Entrance delay acoustic indication
YES
YES
Keypad
Exit delay acoustic indication
YES
YES
Remote control Control function limitation
NO
YES
Control panel
calendar
Control function limitation
NO
YES