Summarized tests
Now the bus load and the error telegrams are measured. During the scan time
(default setting 10 s) the current measured values are displayed every second. In
this way changes can be observed.
Busload
Scan time : 10 s
Bus load : 1 %
Error frames : 0 %
If the measurement is completed successfully, you receive the message "TEST
EXECUTED". The CANcheck has consequently not checked the test result.
Bus load
TEST EXECUTED
NEXT INFO
You can see the test result via "INFO". Here is the beginning of the table with
minimum value, maximum value and average value. The symbols
▼
►
in the
header mean that there are more lines in the table. You can scroll down the table
with the key DOWN. To see the end of a long line, you can move the table in the
display with the key RIGHT.
Busload
▼
►
Scan time : 20 s
MIN MAX AVG
Bus load
Continue the operational tests by returning to the higher order menu with the
ESC key. Start the next test with the virtual key "NEXT" and the OK key.
In this test the CANcheck records all identifiers that are received during the scan
time (default setting 10 s). Then the CANcheck measures the differential and ab-
solute signal level for each identifier.
Copyright IXXAT Automation GmbH
CANcheck Manual, Version 1.2
21