Remote control
All measurement results:
|
|-- Wiring test:
|
| CAN_H -> CAN_L : 65 Ohm[OK]
| CAN_H -> CAN_GND : >1MOhm[OK]
| CAN_H -> CAN_SHLD : >1MOhm[OK]
| CAN_H -> GND : >1MOhm[OK]
|
| CAN_L -> CAN_GND : >1MOhm[OK]
| CAN_L -> CAN_SHLD : >1MOhm[OK]
| CAN_L -> GND : >1MOhm[OK]
|
| CAN_V+ -> CAN_H : 83.6kOhm[OK]
| CAN_V+ -> CAN_L : 83.6kOhm[OK]
| CAN_V+ -> CAN_GND : 84.0kOhm[OK]
| CAN_V+ -> CAN_SHLD : 84.7kOhm[OK]
| CAN_V+ -> GND : 83.6kOhm[OK]
|
| CAN_SHLD -> CAN_GND : >1MOhm
| CAN_SHLD -> GND : >1MOhm
|
| GND -> CAN_GND : >1MOhm
|
|-- Term. resistors:
| 65 Ohm [OK]
|
|-- Line length:
| 97 m
|
|-- Line impedance:
| 109 Ohm [OK]
|
|-- *** END ***
To transfer the test results to the PC, please proceed as follows:
1. Record the transmitted data in the terminal program on the PC. For this,
select Transfer/Text recording in the Hyperterminal program. Please enter a
meaningful path and name for the file and press the "Start" button.
2. At the prompt > in the terminal program, enter the character string
rsho
to view all stored results.
3. Close the file with the recorded data. For this, select Transfer/Text re-
cording/End in the Hyperterminal program.
Then you can edit or print the file with the recorded data.
To integrate the CANcheck in automated test runs, individual tests must be
started from the PC. At the moment only the remote control of the wiring test is
implemented.
Copyright IXXAT Automation GmbH
CANcheck Manual, Version 1.2
65