Summarized tests
To receive an error-free test result, it is now necessary to repeat the tests of the
line parameters. Return to the system menu by pressing the ESC key twice. Start
the tests of the line parameters by pressing the OK key.
Please confirm the test instructions and the result of the wiring test as well as the
test instructions and the result of the measurement of the termination resistors by
pressing the OK key four times.
Now remove the termination resistors at both ends of the CAN network. If
switched off CAN nodes are still connected to the CAN network, the test is only
possible if they have a high resistance between CAN_H, CAN_L and ground.
The line length can only be correctly measured if you have connected the CAN-
check to the line end, where normally one of the two termination resistors of the
CAN network is located.
If the measurement is completed successfully, you receive the message "TEST
EXECUTED". The CANcheck has consequently not checked the test result.
Line length
TEST EXECUTED
NEXT INFO
You receive the test result with the virtual key "INFO".
Line length
96 m
Continue the tests of the line parameters by returning to the higher order menu
with the ESC key. Start the next test with the virtual key "NEXT" and the OK key.
Before the measurement of the line impedance, the next test instructions are dis-
played: