Sensor Wiring
64
Modline 5
4
Sensor Wiring
4.1
Modline 5 Components
The basic Modline 5 system consists of either a standard Sensor or Sensor with Dirty Window Detector
option, interconnecting cable, a POI Power Supply/Signal Interface Box or Terminal Strip Plate and as
possible option, the DPM Digital Panel Meter Interface.
Figure 55: Modline 5 Components
4.2
Modline 5 Sensor System Interfacing
The following figure shows a block diagram overview for interfacing the Modline 5 into a process
monitoring and control system.
Figure 56: Block diagram
POI
Box
or
Terminal Strip
Plate
Interconnecting Cable
Sensor Alarm Relay Contacts
Peak Picker / Track & Hold Remote
Switch Input
RS-485 Digital Communication to
Modline 5 DPM, PLC, Host
Computer or other Device
24Vdc Sensor Power Supply limited
to 2 Amps
Analog Current Output
Selectable 0 - 20 mA or 4 - 20 mA
Scaled to Sensor temperature span or customized for process
Single or multiple series connected differential input devices,
Digital Indicators, Recorders, Controllers, Control Systems
600 Ohm maximum load resistance, including cable resistance
Sensor
T
A
R
G
E
T
Input 4-20 mAdc for Remote
Emissivity/E-Slope or Laser Switch
100 - 240Vac 50/60Hz (POI)
or 24Vdc (TSP)