Operation
Modline 5
95
If the current loop is set for 0 to 20 mA operation, the A–LO function will not appear as a
menu item. The analog output always goes to 0 mA if the measured temperature is below
the Analog Output Zero Sale temperature.
5.7.3
A–HI – Analog Output High Temperature Alarm
Sets the Analog Output current value if the measured temperature is above the temperature that
produces Analog Full Scale Output as determined by the Analog Output Full Scale Temperature Scaling
explained above. Selectable range is 20.0 mA to 24.0 mA.
Analog Output Settings
Navigate from TEMP with
&
▲▼
to AOUT then use
&
▲▼
to SOUT or ZERO or FULL or Fatl or
A-LO or A-HI
Press ENT
to save and return to TEMP display after each function.
Display
Instructions
Display and Limits
SOUT
Press ENT to view the SOUT output current range, 0 to 20 mA or 4 to 20 mA
Use Up / Down Arrows to select output current range.
0-20 or 4-20
ZERO
Press ENT to view temperature corresponding to the selected Analog Output
Current Range minimum value (0 or 4 mA)
Use Up / Down Arrows to set Temperature within the Sensor temperature
range and high limit shown.
Temperature Value
Maximum is 10 F below the
selected FULL temperature
(see below)
See note above for °C
operation.
FULL
Press ENT to view Temperature Corresponding to the Analog Output
Maximum value (20 mA)
Use Up / Down Arrows to set Temperature within the Sensor temperature
range and low limit shown.
Temperature Value
Minimum is 10 F above the
selected ZERO temperature
(see above)
See note above for °C
operation.
Fatl
Press ENT to view the Analog Output selected mA current value.
Use Up / Down Arrows to set the current value.
00.0 to 24.0
A–LO
This function does not appear if the SOUT selected range is 0 to 20 mA.
Press ENT to view the Analog Output selected mA current value.
Use Up / Down Arrows to set the current value.
00.0 to 4.00
A–HI
Press ENT to view the Analog Output selected mA current value.
Use Up / Down Arrows to set the current value.
20.0 to 24.0
5.8
COMM – Setup of RS-485 Digital Communication Configuration
The Modline 5 RS-485 Digital Communication interface permits interchange of ASCII coded
information between the Modline 5 Sensor and
a host computer, PLC (Programmable Logic
Controller),
or any other RS-485 device.
The RS-485 data signal is transmitted on the Yellow and Yellow/White twisted wire pair of the Sensor’s
interconnecting cable. All communication is via half-duplex two wires.
Refer to section 6
Содержание Modline 5
Страница 2: ......
Страница 4: ......
Страница 156: ...Notices 154 Rev L6 Feb 2017 Modline 5 9 Notices ...