Maintenance
Modline 5
125
Status Display
Error Code Details
Error Code
X101
Dirty Window Detected
Dirty front Sensor optics detected. Clean Sensor front window and
mirror. This will only be seen on Sensors with the Dirty Window
Detector Option
Error Code
X102
Out of calibration (M56)
Do not Initiate a Calibration Check during
warm-up. See Section
, page 85, for M52, 5G, and 5R
models.
Calibration check has sensed Sensor out of calibration condition
Note: An out of calibration error may be encountered if the Sensor
temperature is too high or too low. Do not calibrate when an
Alarms for error codes X103, X104, X105, X106 exist.
Caution: Any temperature readings at Analog Output or from RS-
485 Communications must be considered inaccurate
Check Sensor Calibration on a Blackbody Standard
Error Code
X103
Detector block too hot
Detector Temperature is too high.
Check ambient temperature (55 °C maximum) and Sensor internal
case temperature using the RS485 RC Command or with a
temperature measuring device such as a fine thermocouple. If
these temperatures are okay and alarm continues Sensor may
have a malfunction.
Caution: Any temperature readings on rear panel display, at
Analog Output or from RS-485 Communications may be
inaccurate.
Error Code
X104
Detector block too cold
Note: This Error Code is normal during
Sensor warm-up. Warm-up typically lasts
from just a few minutes to 15 minutes.
Detector Temperature is too low
Check ambient temperature (0°C minimum) and Sensor internal
case temperature using the RS485 RC Command or with a
temperature measuring device such as a thermocouple.
If these temperatures are okay and alarm continue, check the
24VDC supply voltage. Sensor may have a long warm-up time if
the voltage not within 5%.
If the power supply is remotely installed, insure the voltage drop
across power supply wires is not causing a low voltage level at the
Sensor.
Caution: Any temperature readings on rear panel display, at
Analog Output or from RS-485 Communications may be
inaccurate.
Error Code
X105
Case temperature too high
Sensor case temperature is below is above specification.
Check ambient temperature (55 °C maximum) and Sensor internal
case temperature using the RS485 RC Command or with a
temperature measuring device such as a thermocouple. If these
temperatures are okay and alarm continues Sensor may have a
malfunction.
Caution: Any temperature readings on rear panel display, at
Analog Output or from RS-485 Communications may be
inaccurate
Содержание Modline 5
Страница 2: ......
Страница 4: ......
Страница 156: ...Notices 154 Rev L6 Feb 2017 Modline 5 9 Notices ...