Goodrive10 Series Mini VFD
Function parameters
-69-
Function
code
Name
Description
Default Modify
P11.03
Overvoltag
e stall
protection
0: Disable
1: Enable
DC bus voltage
Overvoltage stall
point
Output frequency
1
○
P11.04
Overvoltag
e stall
protection
voltage
120
–150% (standard bus voltage) (380V)
136%
○
120
–150% (standard bus voltage) (220V)
120%
P11.05
Current
limit action
selection
The actual increasing ratio is less than the ratio
of output frequency because of the big load
during ACC running. It is necessary to take
measures to avoid overcurrent fault and the
VFD trips.
During the running of the VFD, this function will
detect the output current and compare it with the
limit level defined in P11.06. If it exceeds the
level, the VFD will run at stable frequency in
ACC running, or the VFD will derate to run
during the constant running. If it exceeds the
level continuously, the output frequency will
keep on decreasing to the lower limit. If the
output current is detected to be lower than the
limit level, the VFD will accelerate to run.
Output frequency
Output current
Limiting
point
Set
frequency
ACC
T
T
Constant
speed
Setting range of P11.05:
1
◎
P11.06
Automatic
current
limit level
160.0%
◎
P11.07
The
decreasing
ratio during
current
limit
10.00Hz/
s
◎