Goodrive10 Series Mini VFD
Function parameters
-27-
Function
code
Name
Description
Default Modify
P00.04
Upper limit
of the
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD
which is lower than or equal to the maximum
frequency.
Setting range:P00.05
–P00.03 (Max. output
frequency)
50.00Hz
◎
P00.05
Lower limit
of the
running
frequency
The lower limit of the running frequency is that of
the output frequency of the VFD.
The VFD runs at the lower limit frequency if the
set frequency is lower than the lower limit one.
Note:
Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range:0.00Hz
–P00.04 (Upper limit of the
running frequency)
0.00Hz
◎
P00.06
A
frequency
command
selection
Note:
Frequency A and frequency B cannot use
the same frequency setting mode. The
frequency source can be set by P00.09.
0:Keypad data setting (correspond to the
keypad potentiometer)
Modify the value of function code P00.10 (set
the frequency by keypad) to modify the
frequency by the keypad.
1: AI1 setting (corresponding to keypad
potentiometer)
2: AI2 setting (corresponding to terminal AI)
Analog input terminal sets the frequency. There
are 2 standard analog input terminal, of which
AI1 is adjusted through digital potentiometer, AI2
(0
–10V/0–20mA) can be switched by the
jumper.
Note:
when AI2 selects 0
–20mA input, 20mA
corresponds to 10V.
100.0% of the analog input corresponds to
P00.03,
-100.0%
of
the
analog
input
corresponds to the reverse P00.03.
6: Multi-step speed running setting
The VFD runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the
current running step, and set P10 to select the
0
○
P00.07
B
frequency
command
selection
2
○