Goodrive10 Series Mini VFD
Technical data
-104-
A.1.2.2 Derating due to altitude
When the altitude of the site where the VFD is installed is lower than 1000m, the VFD can
run at the rated power. When the altitude exceeds 1000m, derate by 1% for every increase
of 100m. When the altitude exceeds 3000m, consult the local INVT dealer or office for
details.
A.1.2.3 Derating due to carrier frequency
The VFDs in different power classes are different in carrier frequency. The rated power of a
VFD is defined based on the carrier frequency set in factory. If the carrier frequency
exceeds the factory setting, the power of the VFD is derated by 10% for each increased 1
kHz.
A.2 CE
A.2.1 CE marking
The CE marking on the name plate of a VFD indicates that the VFD is CE-compliant,
meeting the regulations of the European low-voltage directive (2014/35/EU) and EMC
directive (2014/30/EU).
A.2.2 EMC compliance declaration
European union (EU) stipulates that the electric and electrical devices sold in Europe cannot
generate electromagnetic disturbance that exceeds the limits stipulated in related standards,
and can work properly in environments with certain electromagnetic interference. The EMC
product standard (EN 61800-3) describes the EMC standards and specific test methods for
adjustable speed electrical power drive systems. Our products have been compliant with
these EMC regulations.
A.3 EMC regulations
The EMC product standard (EN 61800-3) describes the EMC requirements on VFDs.
Application environment categories
Category I: Civilian environments, including application scenarios where VFDs are directly
connected to the civil power supply low-voltage grids without intermediate transformers
Category II: All environments except those in Category I.
VFD categories
C1: Rated voltage lower than 1000 V, applied to environments of Category I.
C2: Rated voltage lower than 1000 V, non-plug, socket, or mobile devices; power drive
systems that must be installed and operated by specialized personnel when applied to
environments of Category I
Note:
The EMC standard IEC/EN 61800-3 no longer restricts the power distribution of VFDs,