Goodrive10 Series Mini VFD
Fault tracking
-82-
Fault code
Fault type
Possible cause
Solution
OC3
[6] Overcurrent
during constant
speed running
Load transient or
excepetion occurred.
To-ground short circuit or
output phase loss occur.
There is strong external
interference.
larger power.
Check whether the
load is short circuited
(to-ground short circuit
or line-to-line short
circuit) or the rotation
is not smooth.
Check the output
wiring.
Check whether there is
strong interference.
OV1
[7] Overvoltage
during acceleration
Exception occurred to
input voltage.
There is large energy
feedback.
Check the input power.
Check whether load
deceleration time is too
short, or the motor
starts during rotating.
Install dynamic braking
units.
OV2
[8] Overvoltage
during deceleration
OV3
[9] Overvoltage
during constant
speed running
UV
[10] Bus
undervoltage
Grid voltage is too low.
Check
grid
input
power.
OL1
[11] Motor overload
Grid voltage is too low.
Rated motor current is
set improperly.
Motor stall or load jumps
violently.
Check grid voltage.
Reset
rated
motor
current.
Check the load and
adjust torque boost.
OL2
[12] VFD overload
Acceleration is too fast.
The motor in rotating is
restarted.
Grid voltage is too low.
Load is too large.
The motor power is too
small.
Increase acceleration
time.
Avoid
restart
after
stop.
Check grid voltage.
Select the VFD with
larger power.
Select a proper motor.
OH1
[15] Rectifier
module overheat
Air duct is blocked or fan
is damaged.
Ambient temperature is
too high.
Long-time overload
running.
Ventilate the air duct or
replace the fan.
Lower the ambient
temperature.
OH2
[16] Inverter module
overheat