Goodrive10 Series Mini VFD
Function parameters
-44-
Function
code
Name
Description
Default
Modify
During running, the direction control is as
follows:
Sln
REV
Previous
direction
Present
direction
ON
OFF→ON
Forward
Reverse
Reverse
Forward
ON
ON→OFF
Reverse
Forward
Forward
Reverse
ON→
OFF
ON
Decelerate to stop
OFF
Sln: 3-wire control, FWD: Forward running,
REV: Reverse running
3: 3-wire control 2; This mode defines Sin as
the enabling terminal, and the running
command is generated by FWD or REV, but
the direction is controlled by both FWD and
REV. During running, the Sin terminal needs
to be closed, and terminal FWD or REV
generates a rising edge signal to control the
running and direction of VFD; the VFD needs
to be stopped by disconnecting terminal Sin.
COM
SB2
SB1
FWD
REV
SIn
SB3
Sln
FWD
REV
Direction
ON
OFF→ON
ON
Forward
OFF
Reverse
ON
ON
OFF→
ON
Forward
OFF
Reverse
ON→
OFF
/
/
Decelerat
e to stop
/
/
Содержание GD10-0R2G-2-B
Страница 1: ......
Страница 125: ...66001 00099...