Goodrive10 Series Mini VFD
Communication protocol
-93-
7.3.3 Command code 08H, diagnosis
Sub-function code description:
Sub-function code
Description
0000
Return data based on query requests
For example, to query about the circuit detection information about the VFD whose address
is 01H, the query and return strings are the same, and the formats are described in the
following tables.
RTU master command
RTU slave command
START
T1-T2-T3-T4
START
T1-T2-T3-T4
ADDR
01H
ADDR
01H
CMD
08H
CMD
08H
MSB of
sub-function code
00H
MSB of
sub-function code
00H
LSB of sub-function
code
00H
LSB of
sub-function code
00H
MSB of data
12H
MSB of data
12H
LSB of data
ABH
LSB of data
ABH
LSB of CRC CHK
ADH
LSB of CRC CHK
ADH
MSB of CRC CHK
14H
MSB of CRC
CHK
14H
END
T1-T2-T3-T4
END
T1-T2-T3-T4
7.3.4 Data address definition
This section describes the address definition of communication data. The addresses are
used for controlling the running, obtaining the status information, and setting function
parameters of the VFD.
7.3.4.1 Function code address format rules
The parameter address occupies 2 bytes with the fact that the MSB is in the front and the
LSB is in the behind. The range of MSB and LSB are: MSB
—00–ffH; LSB—00–ffH. The
MSB is the group number before the radix point of the function code and the LSB is the
number after the radix point. But both the MSB and the LSB should be changed into hex.
For example P05.05, the group number before the radix point of the function code is 05,
then the MSB of the parameter is 05, the number after the radix point 05, then the LSB of
the parameter is 05, then the function code address is 0505H and the parameter address of
P10.01 is 0A01H.
Note:
P29 group is the factory parameter which cannot be read or changed. Some
parameters cannot be changed when the VFD is in the running state and some
parameters cannot be changed in any state. The setting range, unit and related