Goodrive10 Series Mini VFD
Function parameters
-43-
Function
code
Name
Description
Default
Modify
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2, the enabling separated
from the direction. In this mode, FWD is the
enabling terminal. The direction depends on
the defined REV state.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Stopping
Forward
running
Reverse
running
2: 3-wire control 1; This mode defines Sin as
the enabling terminal, and the running
command is generated by FWD, while the
direction is controlled by REV. During
running, the Sin terminal needs to be closed,
and terminal FWD generates a rising edge
signal, then the VFD starts to run in the
direction set by the state of terminal REV; the
VFD needs to be stopped by disconnecting
terminal Sin.
COM
K
SB2
SB1
FWD
REV
SIn
Содержание GD10-0R2G-2-B