Optidrive P2 Elevator User Guide V2.30
Mechanical Installation
www.InvertekDrives.com
Guidelines for mounting (IP55 Units)
o
Before mounting the drive, ensure that the chosen location meets the environmental condition requirements shown in section 18.1.
o
The drive must be mounted vertically, on a suitable flat surface.
o
The minimum mounting clearances as shown in the table below must be observed.
o
The mounting site and chosen mountings should be sufficient to support the weight of the drives.
o
Using the drive as a template, or the dimensions shown in section 5.7, mark the locations required for drilling.
o
The drive should be mounted using M8 (Frame Sizes 4 & 5) mounting bolts.
Drive
Size
X
Above &
Below
Y
Either
Side
mm
in
mm
in
4
200
7.87
10
0.39
5
200
7.87
10
0.39
6
200
7.87
10
0.39
Note :
Typical drive heat losses are approximately 3% of
operating load conditions.
Above are guidelines only and the operating
ambient temperature of the drive MUST be
maintained at all times.
Removing the Terminal Cover
Frame Size 4
Frame Size 5
Using a suitable flat blade
screwdriver, rotate the two
retaining screws indicated until the
screw slot is vertical.
Using a suitable flat blade
screwdriver, rotate the four
retaining screws indicated until
the screw slot is vertical.
Terminal Cover Release Screws