Optidrive P2 Elevator User Guide V2.30
Technical Data
www.InvertekDrives.com
18.
Technical Data
Environmental
Ambient temperature range:
Operational
: -10 … 50
C IP20 Units
: - 10 … 40°C IP55 Units (UL Approved)
: -10 … 50°C IP55 Units (Non UL Approved with derating, refer to section
18.5.1 for Derating for Ambient Temperature Information)
Storage and Transportation
: -40
C … 60
C
Max altitude for rated operation
: 1000m (Refer to section 18.5 for Derating Information)
Relative Humidity
: < 95% (non-condensing)
Note
:
Drive must be Frost and moisture free at all times
Installation above 2000m is not UL approved
Input voltage ranges
Depending upon model and power rating, the drives are designed for direct connection to the following supplies:
Mains supply.
Model Number
Supply Voltage
Phases
Frequency
ODL-2-x4xxx-3xxxx
380 – 480 Volts + / - 10%
3
50 – 60Hz + / - 5%
ODL-2-x2xxx-3xxxx
200 – 240 Volts + / - 10%
3
50 – 60Hz + / - 5%
ODL-2-x2xxx-1xxxx
200 – 240 Volts + / - 10%
1
50 – 60Hz + / - 5%
Rescue Mode (UPS) supply.
Model Number
Supply Voltage
ODL-2-x4xxx-3xxxx
Sine wave Output UPS = 205 -240VAC
In order to support Simulated Sine Wave type UPS supplies the DC bus as measured by parameter P0-20 must be in the
range 295Vdc - 400Vdc.
All Optidrive P2 Elevator drives have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping. For input
supplies which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia Pacific including China) Invertek
Drives recommends the installation of input line reactors.