Description of Function Codes
MD380 User Manual
- 240 -
F
unction Code
Parameter Name
Setting Range
Default
AC-12
AO1 target voltage 1
0.500–4.000 V
F
actory-corrected
AC-13
AO1 measured voltage 1
0.500–4.000 V
F
actory-corrected
AC-14
AO1 target voltage 2
6.000–.999 V
F
actory-corrected
AC-15
AO1 measured voltage 2
6.000–9.999 V
F
actory-corrected
AC-16
AO2 target voltage 1
0.500–4.000 V
F
actory-corrected
AC-17
AO2 measured voltage 1
0.500–4.000 V
F
actory-corrected
AC-18
AO2 target voltage 2
6.000–9.999 V
F
actory-corrected
AC-19
AO2 measured voltage 2
6.000–9.999 V
F
actory-corrected
AC-20
AI2 measured current 1
0.000–20.000 mA
F
actory corrected
AC-21
AI2 sampling current 1
0.000–20.000 mA
F
actory corrected
AC-22
AI2 measured current 2
0.000–20.000 mA
F
actory corrected
AC-23
AI2 sampling current 2
0.000–20.000 mA
F
actory corrected
AC-24
AO1 ideal current 1
0.000–20.000 mA
F
actory corrected
AC-25
AO1 sampling current 1
0.000–20.000 mA
F
actory corrected
AC-26
AO1 ideal current 2
0.000–20.000 mA
F
actory corrected
AC-27
AO1 sampling current 2
0.000–20.000 mA
F
actory corrected
These parameters are used to correct the AO.
They have been corrected upon delivery. When you resume the factory values, these
parameters will be restored to the factory-corrected values. You need not perform correction
in the applications.
Target voltage indicates the theoretical output voltage of the AC drive. Measured voltage
indicates the actual output voltage value measured by instruments such as the multimeter.
Group U0: Monitoring Parameters
Group U0 is used to monitor the AC drive's running state. You can view the parameter
values by using operation panel, convenient for on-site commissioning, or from the host
computer by means of communication (address: 0x7000-0x7044).
U0-00 to U0-31 are the monitoring parameters in the running and stop state defined by F7-
03 and F7-04. For more details, see Table 6-1.
F
unction Code
Parameter Name
Display Range
U0-00
Running frequency
0.00–320.00 Hz (
F
0-22 = 2)
U0-01
Set frequency
0.00–3200.0 Hz (
F
0-22 = 1)
These two parameters display the absolute value of theoretical running frequency and set
frequency. For the actual output frequency of the AC drive, see U0-19.
F
unction Code
Parameter Name
Display Range
U0-02
B
us voltage
0.0–3000.0 V
It displays the AC drive's bus voltage.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...