Operation, Display and Application Examples
MD380 User Manual
- 72 -
Figure 4-30 Driving multiple motors
F
0-01 = 2
F
0-01 = 0 or 1
F
0-01 = 0 or 1
F
0-24
= 0
F
0-24
= 1
F
0-24
= 2
F
0-24
= 3
Motor 1 Motor 2 Motor 3 Motor 4
In the vector control mode , up to 4 motors
can be driven at different time . The motor
parameters are restored respectively .
In the vector control mode ,
multiple motors cannot be
driven simultaneously.
In the V/
F control mode
,
multiple motors can be
driven simultaneously.
4.10 Use of DI Terminals
The control board provides five DI terminals DI1 to DI5. You can obtain another DI terminals
DI6 to DI10 by installing an I/O extension card.
The internal hardware of DI terminals are configured with 24 VDC power supply for
detection. You can input a signal to a DI terminal of the AC drive only by shorting the DI
terminal and COM.
By default, F4-38 = 0000 and F4-39 = 0000. When a DI terminal is shorted to COM, it is
active (logic 1). When a DI terminal is not shorted to COM, it is inactive (logic 0).
You can change the DI terminal active mode. That is, a DI terminal is inactive (logic 0) when
being shorted with COM, and active (logic 1) when being not shorted to COM. In this case,
it is necessary to change the corresponding bit in F4-38 and F4-39 (these two parameters
respectively specifying the active mode setting of DI1 to DI5 and DI16 to DI10) to 1.
The AC drive also provides F4-10 (DI filter time) for the DI signal to improve the anti-
interference level. For DI1 to DI3, the AC drive provides the DI signal delay function,
convenient for some applications requiring delay.
Figure 4-31 DI delay setting
t
DI hardware
signal
Internal DI
signal
T
T
DI1
delay set in F
4-35
DI2
delay set in F
4-36
DI3
delay set in F
4-37
The preceding 10 DI terminals can be de
fi
ned in function codes
F
4-00 to
F
4-09. Each DI can be
allocated with their respective function from the 50 functions.
F
or details, see descriptions of
F
4-
00 to
F
4-09.
The hardware design allows only DI5 to receive high-speed pulse signal. If high-speed pulse
count is required, use DI5.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...