Description of Function Codes
MD380 User Manual
- 168 -
Figure 6-10 Setting of three-line mode 2
MD380
DI1
COM
Digital common
DI2
RUN command
Running direction
DI3
Stop running
SB
1
SB
2
K
Running
direction
K
0
1
Forward
Reverse
RUN
button
Stop
button
As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is
pressed to be ON; the AC drive instructs forward rotation when K is OFF and instructs
reverse rotation when K is ON. The AC drive stops immediately after SB1 becomes
OFF. During normal startup and running, SB1 must remain ON. The AC drive's running
state is determined by the final actions of SB1, SB2 and K.
F
unction Code
Parameter Name
Setting Range
Default
F
4-12
Terminal UP/DOWN rate
0.01–65.535 Hz/s
1.00 Hz/s
It is used to adjust the rate of change of frequency when the frequency is adjusted by means
of terminal UP/DOWN.
•
If F0-22 (Frequency reference resolution) is 2, the setting range is 0.001–65.535 Hz/s.
•
If F0-22 (Frequency reference resolution) is 1, the setting range is 0.01–655.35 Hz/s.
F
unction Code
Parameter Name
Setting Range
Default
F
4-13
AI curve 1 minimum input
0.00 V to
F
4-15
0.00 V
F
4-14
Corresponding setting of AI
curve 1 minimum input
-100.00%–100.0%
0.0%
F
4-15
AI curve 1 maximum input
F
4-13 to 10.00 V
10.00 V
F
4-16
Corresponding setting of AI
curve 1 maximum input
-100.00%–100.0%
100.0%
F
4-17
AI1
fi
lter time
0.00–10.00s
0.10s
These parameters are used to define the relationship between the analog input voltage and
the corresponding setting. When the analog input voltage exceeds the maximum value (F4-
15), the maximum value is used. When the analog input voltage is less than the minimum
value (F4-13), the value set in F4-34 (Setting for AI less than minimum input) is used.
When the analog input is current input, 1 mA current corresponds to 0.5 V voltage.
F4-17 (AI1 filter time) is used to set the software filter time of AI1. If the analog input is liable
to interference, increase the value of this parameter to stabilize the detected analog input.
However, increase of the AI filter time will slow the response of analog detection. Set this
parameter properly based on actual conditions.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...