Description of Function Codes
MD380 User Manual
- 158 -
These six parameters are used to define the multi-point V/F curve.
The multi-point V/F curve is set based on the motor's load characteristic. The relationship
between voltages and frequencies is:
V1 < V2 < V3, F1 < F2 < F3
At low frequency, higher voltage may cause overheat or even burnt out of the motor and
overcurrent stall or overcurrent protection of the AC drive.
Figure 6-5 Setting of multi-point V/F curve
Frequency
%
Voltage
%
V3
Fb
F
1
V1
Vb: Rated motor voltage
V1-V3: 1st, 2nd and 3rd voltage
percentages of multi -point V/
F
Fb
: Rated motor running frequency
F
2
F
3
V2
Vb
F
1-
F
3: 1st, 2nd and 3rd frequency
percentages of multi -point V/
F
F
unction Code
Parameter Name
Setting Range
Default
F
3-09
V/
F
slip compensation gain
0%–200.0%
0.0%
This parameter is valid only for the asynchronous motor.
It can compensate the rotational speed slip of the asynchronous motor when the load of the
motor increases, stabilizing the motor speed in case of load change. If this parameter is set
to 100%, it indicates that the compensation when the motor bears rated load is the rated
motor slip. The rated motor slip is automatically obtained by the AC drive through calculation
based on the rated motor frequency and rated motor rotational speed in group F1.
Generally, if the motor rotational speed is different from the target speed, slightly adjust this
parameter.
F
unction Code
Parameter Name
Setting Range
Default
F
3-10
V/
F
over-excitation gain
0–200
64
During deceleration of the AC drive, over-excitation can restrain rise of the bus voltage,
preventing the overvoltage fault. The larger the over-excitation is, the better the restraining
result is.
Increase the over-excitation gain if the AC drive is liable to overvoltage error during
deceleration. However, too large over-excitation gain may lead to an increase in the output
current. Set F3-09 to a proper value in actual applications.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...