Table 6-5 Functions of output terminals
Value
F
unction
Description
0
No output
The terminal has no function.
1
AC drive running
When the AC drive is running and has output frequency
(can be zero), the terminal becomes ON.
2
F
ault output (stop)
When the AC drive stops due to a fault, the terminal
becomes ON.
3
F
requency-level
detection
F
DT1 output
Refer to the descriptions of
F
8-19 and
F
8-20.
4
F
requency reached
Refer to the descriptions of
F
8-21.
5
Z
ero-speed running
(no output at stop)
If the AC drive runs with the output frequency of 0, the
terminal becomes ON. If the AC drive is in the stop state,
the terminal becomes O
FF
.
6
Motor overload
pre-warning
The AC drive judges whether the motor load exceeds the
overload pre-warning threshold before performing the
protection action. If the pre-warning threshold is exceeded,
the terminal becomes ON.
F
or motor overload parameters,
see the descriptions of
F
9-00 to
F
9-02.
7
AC drive overload pre-
warning
The terminal becomes ON 10s before the AC drive overload
protection action is performed.
8
Set count value
reached
The terminal becomes ON when the count value reaches
the value set in
FB
-08.
9
Designated count
value reached
The terminal becomes ON when the count value reaches
the value set in
FB
-09.
10
Length reached
The terminal becomes ON when the detected actual length
exceeds the value set in
FB
-05.
11
PLC cycle complete
When simple PLC completes one cycle, the terminal
outputs a pulse signal with width of 250 ms.
12
Accumulative running
time reached
If the accumulative running time of the AC drive exceeds
the time set in
F
8-17, the terminal becomes ON.
13
F
requency limited
If the set frequency exceeds the frequency upper limit or
lower limit and the output frequency of the AC drive reaches
the upper limit or lower limit, the terminal becomes ON.
14
Torque limited
In speed control mode, if the output torque reaches the
torque limit, the AC drive enters the stall protection state
and meanwhile the terminal becomes ON.
15
Ready for RUN
If the AC drive main circuit and control circuit become
stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
16
AI1 larger than AI2
When the input of AI1 is larger than the input of AI2, the
terminal becomes ON.
17
F
requency upper limit
reached
If the running frequency reaches the upper limit, the
terminal becomes ON.
18
F
requency lower limit
reached (no output at
stop)
If the running frequency reaches the lower limit, the terminal
becomes ON. In the stop state, the terminal becomes O
FF
.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...