MD380 User Manual Desc
ription of Function Codes
- 143 -
F
unction Code
Parameter Name
Setting Range
Default
F
0-11
Source of frequency upper limit
0: Set by
F
0-12
1: AI1
2: AI2
3: AI3
4: Pulse setting (DI5)
5: Communication
setting
0
It is used to set the source of the frequency upper limit, including digital setting (F0-12), AI,
pulse setting or communication setting. If the frequency upper limit is set by means of AI1,
AI2, AI3, DI5 or communication, the setting is similar to that of the main frequency source X.
For details, see the description of F0-03.
For example, to avoid runaway in torque control mode in winding application, you can set
the frequency upper limit by means of analog input. When the AC drive reaches the upper
limit, it will continue to run at this speed.
F
unction Code
Parameter Name
Setting Range
Default
F
0-12
F
requency upper limit
F
requency lower limit (
F
0-14) to
maximum frequency (
F
0-10)
50.00 Hz
This parameter is used to set the frequency upper limit.
F
unction Code
Parameter Name
Setting Range
Default
F
0-13
F
requency upper limit
offset
0.00 Hz to maximum frequency
(
F
0-10)
0.00 Hz
If the source of the frequency upper limit is analog input or pulse setting, the final frequency
upper limit is obtained by adding the offset in this parameter to the frequency upper limit set
in F0-11.
F
unction Code
Parameter Name
Setting Range
Default
F
0-14
F
requency lower limit
0.00 Hz to frequency upper limit (
F
0-12)
0.00 Hz
If the frequency reference is lower than the value of this parameter, the AC drive can stop,
run at the frequency lower limit, or run at zero speed, determined by F8-14.
F
unction Code
Parameter Name
Setting Range
Default
F
0-15
Carrier frequency
0.5–16.0 kHz
Model dependent
It is used to adjust the carrier frequency of the AC drive, helping to reduce the motor noise,
avoiding the resonance of the mechanical system, and reducing the leakage current to the
earth and interference generated by the AC drive.
If the carrier frequency is low, output current has high harmonics, and the power loss and
temperature rise of the motor increase.
If the carrier frequency is high, power loss and temperature rise of the motor declines.
However, the AC drive has an increase in power loss, temperature rise and interference.
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...