MD380 User Manual Desc
ription of Function Codes
- 167 -
As shown in the preceding figure, if K1 is ON, the AC drive instructs forward rotation
when K2 is OFF, and instructs reverse rotation when K2 is ON. If K1 is OFF, the AC
drive stops.
•
2: Three-line mode 1
In this mode, DI3 is RUN enabled terminal, and the direction is decided by DI1 and DI2.
The parameters are set as below:
F
unction Code
Parameter Name
Value
F
unction Description
F
4-11
Terminal command mode
2
Three-line 1
F
4-00
DI1 function selection
1
F
orward RUN (
F
WD)
F
4-01
DI2 function selection
2
Reverse RUN (REV)
F
4-02
DI3 function selection
3
Three-line control
Figure 6-9 Setting of three-line mode 1
MD380
DI1
COM Digital common
DI2
Forward RUN
(
FWD
)
Reverse RUN (REV)
DI3 RUN enabled
SB
1
SB
2
SB
3
Forward
button
Reverse
button
Stop
button
As shown in the preceding figure, if SB1 is ON, the AC drive instructs forward rotation
when SB2 is pressed to be ON and instructs reverse rotation when SB3 is pressed to
be ON. The AC drive stops immediately after SB1 becomes OFF. During normal startup
and running, SB1 must remain ON. The AC drive's running state is determined by the
final actions on SB1, SB2 and SB3.
•
3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the
direction is decided by DI2. The parameters are set as below:
F
unction Code
Parameter Name
Value
F
unction Description
F
4-11
Terminal command mode
3
Three-line 2
F
4-00
DI1 function selection
1
RUN enabled
F
4-01
DI2 function selection
2
F
orward or reverse direction
F
4-02
DI3 function selection
3
Three-line control
Содержание HD380-5T0.7GB
Страница 1: ...High Performance AC Drive MD380...
Страница 9: ......
Страница 10: ...1 Safety Information and Precautions...
Страница 17: ...Safety Information and Precautions MD380 User Manual 16...
Страница 18: ...2 Product Information...
Страница 29: ...Product Information MD380 User Manual 28...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 46: ...4 Operation Display and Application Examples...
Страница 79: ...Operation Display and Application Examples MD380 User Manual 78...
Страница 80: ...5 Function Code Table...
Страница 136: ...6 Description of Function Codes...
Страница 248: ...7 EMC...
Страница 260: ...8 Selection and Dimensions...
Страница 285: ...Selection and Dimensions MD380 User Manual 284...
Страница 286: ...9 Maintenance and Troubleshooting...
Страница 298: ...MD380 Series High Performance AC Drive...