ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Function
Introduction AS-i data
33
Description of the IO code for digital slaves
5349
Structure slave profile = S-[IO-Code].x.x
Function of the periphery bit
IO code
(hex)
IO code
(bits 3…0)
D3
D2
D1
D0
0
0000
input input input input
1 0001 output
input
input
input
2
0010
input / output
input
input
input
3 0011 output
output
input
input
4
0100
input / output
input / output
input
input
5 0101 output
output
output
input
6
0110
input / output
input / output
input / output
input
7
0111
input / output
input / output
input / output
input / output
8
1000
output output output output
9 1001
input
output
output
output
A
1010
input / output
output
output
output
B 1011
input
input
output
output
C
1100
input / output
input / output
output
output
D 1101
input
input
input
output
E
1110
input / output
input / output
input / output
output
F 1111
not
allowed
Description of the ID code (selection)
5351
Structure slave profile = S-x.[ID-Code].x
ID code
(hex)
ID code
(bits 3…0)
Description
0
0000
4 I/O connections for binary sensors and/or actuators with 1 signal each
1
0001
2 dual-signal I/O connections for binary sensors and/or actuators with 2 signals each
A
1010
slave operates in the extended addressing mode (B slave or A/B slave)
B
1011
slave corresponds to Safety-at-Work
F 1111
manufacturer-specific
device
(cannot be replaced with products from other manufacturers)