![IFM Ecomat 300 AC1375 Скачать руководство пользователя страница 464](http://html1.mh-extra.com/html/ifm/ecomat-300-ac1375/ecomat-300-ac1375_device-manual_3912477464.webp)
ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Operation
Display slave data
464
.
AS-i 1 Slave 18A
Slave Profile
(hex) IO ID ID1 ID2
Curr: 7 3 F E
Proj: 7 3 F E
MORE
67
ESC
Step 12:
AC1375: Menu screen number = 35
> Display of configuration data of the slave:
Current: current value of the slave,
here: slave type = S-7.3.E,
or, if the slave is not activated on the master:
display "F F F F",
Projected: value which is entered in the projection table.
►
Press [ ] or [ ] to scroll to any other slave address.
►
Scroll to the next screen with [MORE].
Alternatively:
►
Press [ESC] to return to the screen in step 5.
.
AS-i 1 Slave 6A
Parameters
Current: 0111 [ 07h ]
Projected:0111 [ 07h ]
MORE
71
ESC
Step 13:
AC1375: Menu screen number = 39
> Display of the parameters of the slave as binary value and as hex
value:
Default value: "
1111 [0Fh]
":
Current: current value of the slave,
Projected: value which is entered in the projection table.
►
Press [ ] or [ ] to scroll to any other slave address.
►
Scroll to the next screen with [MORE].
Alternatively:
►
Press [ESC] to return to the screen in step 5.
AS-i 1 Slave 7
Telegram Error
12
RET
74
ESC
Step 14:
AC1375: Menu screen number = 42
> Display of the number of telegram errors.
►
Press [ ] or [ ] to scroll to any other slave address.
►
Press [RET] to return to the screen in step 6.
OR:
►
Press [ESC] to return to the start screen.