Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Troubleshooting
RTS errors – error codes R01...R43
499
Error message
Cause(s)
Remedy
R39 reserved
––
R40
Const. data checksum error
A checksum error occurred in the const. areas
(character sets, system language, user language)
of the runtime system.
►
Reprogram the firmware or send the device
to the after-sales service.
R41 reserved
––
R42 reserved
––
R43 reserved
––
R44
Invalid AS-i command
►
Correct command number to a valid value.
R45
DP module 12 illegal word access
When configuring the Profibus DP modules, an
invalid value (odd address) was detected for the
memory to be transmitted.
►
Check and correct the defined data lengths
of the modules 1...11 in the GSD file.
R46
Internal DP stack error
A fatal error was detected in the Profibus DP
stack.
►
Reprogram the firmware or send the device
to the after-sales service.